Main Menu - User Programming
3.2.2 General/NAC Options

General Options

Select whether the NFC will function for Fire Evacuation, Mass Notification, or a Combination of both.
Unit Operation
When Combo or Mass Notification is selected for Unit Operation, select whether Mass Notification events or Fire Evac-
Event Priority
uation events will take priority in the system. If Mass Notification is selected as the Unit Operation with the Event Priority set to Fire
Evacuation, the NFC will be a mass notification only system but will allow the FACP to override it if a fire alarm sounds. If Mass Noti-
fication is selected as the Unit Operation with the Event Priority also set to Mass Notification, the NFC will not have any fire evacuation
capabilities and will report mass notification events to the FACP. In this configuration, FACP outputs can be turned off for mass notifica-
tion events if desired.
FACP Data Bus Control
Bus or ANN-Bus.
FACP Data Bus Address
ACS-bus protocol, address 01 must be enabled in the FACP programming. When using the ANN-Bus protocol, the FACP will automati-
cally detect the audio system connection during annunciator auto-configuration. No ANN-Bus address selection is necessary at the
FACP. Enter the NFC's address (1-8) here. If FACP control of the NFC is not selected, enter 0.
24 Hour Resound
alarms and troubles after the panel has been silenced.
Canadian Configuration
information.
Class A / Style Z
Select enable if all circuits on the NFC will operate in Class A (Style Z) or disabled if all circuits will operate in Class
B (Style Y).
Canadian Isolator Modules
ules" on page 83 for more information.
The reporting of a loss of AC power using the AC Loss relay output can be delayed by programming the length of the
AC Loss Delay
desired delay. The factory default setting is 2 hours. Options are 0, 2, 6, 12, or 23 hours.
Secondary Amplifier
circuits. If an NFC-BDA-25/70V is not installed, select none.
Primary Amp 70 VAC
verted from 25V to 70V by installing the NFC-XRM-70V. If this transformer has been installed, be sure that SW5 on the main control
board has been set to "70V" operation. Use this field to record the amplifier's settings.
Secondary Amp 70 VAC
70V has been installed and a secondary amplified is required, model number NFC-BDA-70V must be used. Use this field to record
which model has been installed in the system.
External Audio Input
tion as Background Music or External Paging - Night Ring. See Section 4.4.15 for more information.
The default IP address of 169.254.3.3 can be changed to another address with numbers from 0-255. Changing the IP address
IP Address
is suggested for a higher level of security on the system's programming. This number should be written down and stored in a safe loca-
tion.
Enter a label for this NFC system. Up to 80 character may be entered.
Identification
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
If an FACP will directly communicate with the NFC, select which communication protocol will be used, ACS-
This field has no effect on programming and is used for informational purposes only. When using the FACP
As enabled (default), the 24 Hour Resound feature causes the piezo on the NFC to sound a reminder 'beep' for
Selecting enable will configure the panel to comply with Canadian requirements. See Appendix C for more
If audio isolator modules are required in the system, select enabled. Refer to "Audio Room Isolator Mod-
if an NFC-BDA-25/70V is installed, select whether it will be used as a backup amplifier or for secondary speaker
This field has no effect on programming and is used for informational purposes only. The system can be con-
This field has no effect on programming and is used for informational purposes only. When the NFC-XRM-
If there is a permanent connection to TB5 on the display board, select whether the external audio input will func-
Figure 3.3 General Options
Programming
53