The Notifier FirstCommand NFC-50/100 is a single channel, 50 watt, 25 V
fire applications, mass notification applications, or both. The NFC-50/100 comes standard with one speaker circuit. The panel provides
the ability to record fourteen field programmable messages (up to 60 seconds each) with an integral microphone or from an external
audio source. An integral power supply with battery charger supplies operational power. A 50 watt audio amplifier is built into each
panel. An optional second 50 watt amplifier (NFC-BDA-25/70V) is also available for backup purposes or to provide an additional 50
watts. The backup amplifier is available in either 25 volts or 70 volts depending on which application is necessary.
Automatic activation of the NFC-50/100 by an FACP is possible via eight Command Input Circuits (CMD) or via the ACS/ANN Bus
serial communications link from the FireWarden-100X, FireWarden-100-2, NFS2-640, and NFS-320 FACPs.
Two Command Input Circuits can be independently field programmed for activation by an FACP Notification Appliance Circuit reverse
polarity or by closure of a supervised normally open contact and six Command Input Circuits activate on contact closure. CMD 1 and
CMD 2 provide terminals for NAC input and output to allow installation of the audio panel anywhere along the NAC circuit being used
to activate it.
If the message generator fails, the system automatically reverts to a backup tone generator.
Power is fed independently to each amplifier so that a short circuit in one amplifier will not shut down the other. Full output power of 50
watts per amplifier is generated while in a low battery condition. Power is not diminished when the optional 70 V
ule is installed. Audio is amplified utilizing modern integrated circuits as opposed to transformer technology. This provides for very low
signal distortion for crystal clear audio.
Primary applications for the audio panels include protecting structures such as military facilities, restaurants, schools, auditoriums,
places of worship, buildings with occupancies over 50, etc. The NFC-50/100 is designed to interface directly to addressable or conven-
tional (CMD inputs 1-8) fire alarm control panels or can be used with the NFC-50/125DA panel to distribute audio in systems that
require more than 100 watts.
For Canadian applications, refer to Appendix C on page 83.

1.1 Product Features

Modular design for maximum system flexibility and easy expansion
Removable terminal blocks for ease of servicing and module replacement
50 watts of 25 V
2 amp Notification Appliance Circuit (NAC) output, sync generator, or follower for protocols:
– System Sensor
– Wheelock
– Gentex
Optional 70.7 V
in standby, alarm and when background music is playing with this optional transformer installed)
Eight Command Input Circuits to activate messages 1 to 8:
– CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification Appliance Circuits (reverse polarity) or
contact closures
– CMD3-CMD8 are activated by contact closures
Speaker Circuits
– single Style Y (Class B) or Style Z (Class A) speaker circuit
– two Style Y (Class B) or Style Z (Class A) speaker circuits (with optional NFC-BDA-25/70V Audio Amplifier installed)
– eight Style Y (Class B) or Style Z (Class A) speaker circuits (with optional NFC-BDA-25/70V and NFC-CE6 installed)
NFC-50/100 can be controlled by an FACP via the ANN/ACS (EIA-485) link. ACS compatible FACPs include the FireWarden-
100X, FireWarden-100-2, NFS2-640, and NFS-320. ANN compatible FACPs include the FireWarden-100-2.
Integral supervised microphone
Microphone time-out feature which reverts back to prerecorded message if emergency page exceeds the programmed time
Up to 14 recorded messages
14 prerecorded messages for fire, emergency, and weather alerts
Field-selectable message and custom message recording capability using the local microphone, a USB port, or an external audio
input
External Audio Input can be used for background music
Up to 60 second message duration for all messages
Integral tone generators field selectable for multiple tone types
Powered by integral AC power supply or batteries during AC fail
Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss
Piezo sounder for local trouble
100 event history log
Three Form-C relays:
– AC Power Loss Relay - TB1
– System Trouble Relay - TB2
– MNS Active - TB3
500 mA (0.5A) Special Application (auxiliary power) output for addressable modules when interfaced with compatible addressable
FACPs and End-of-Line power supervision relays
12

Section 1: Product Description

audio power (expandable to 100 watts)
RMS
conversion transformer available for the primary amplifier (note that speaker wiring continues to be supervised
RMS
, emergency voice evacuation panel that may be used for
RMS
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
transformer mod-
RMS

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier nfc-50/100eNotifier firstcommand seriesNotifier firstcommand nfc-50/100Notifier firstcommand nfc-50/100e

Table of Contents