2.12 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at
least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the NFC-50/100 with two speaker
circuits is shown below.
Power-limited
Circuits
(Class 2)
Power-limited
Circuits
(Class 2)
AC Power
Nonpower-
limited Circuit
NOTE: Use of the 70V transformer makes all power-limited circuits Class 3.
42
Power-limited Circuits
(Class 2)
limited circuit
Figure 2.31 Typical Wiring Diagram for UL Power-limited Requirements
Power-limited Circuits
to batteries
nonpower-
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
UL Power-limited Wiring Requirements
(Class 2)
Power-limited
Circuits
(Class 2)
Power-limited
Circuits
(Class 2)