Nac Options; Console Control - Honeywell NOTIFIER NFC-50/100 Instruction Manual

Table of Contents

Advertisement

Programming

NAC Options

The NAC circuit can be programmed to activate for specific applications. Select Mass Notification to turn on the NAC cir-
NAC Type
cuit only for a mass notification event, Fire Evacuation to turn on the NAC circuit only for a fire evacuation event, Both to turn on the
NAC circuit for both mass notification and fire evacuation events, or Follow Input to have the NAC follow the input from an external
source (connections to TB18). To use Both, the Unit Operation must be set to Combination. Refer to "Unit Operation" on page 53.
The programmer can select the notification appliance coding or strobe synchronization by selecting the corresponding
NAC Protocol
drop-down box. Select System Sensor for System Sensor synchronization, Wheelock, for Wheelock synchronization, Gentex for Gentex
synchronization, or Steady, for a continuous output with no coding.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit. Following
is a list of the strobes that have been tested with the NFC and the maximum number that can be connected to each NAC. Make sure that
the NAC maximum current is not exceeded.
Selects whether this power is Constant or Resettable use from TB17.
Aux Power
Speaker Volume Control NAC
ual volume setting for telephone paging and background music for a specific speaker or speaker zone, select Enabled.

Console Control

Priority can be assigned to the operator consoles so that the primary operator interface can always override the func-
Console Priority
tions at the local operator consoles or remote microphones. Select POC->LOC->RM for console priority. Selecting Equal for priority
allows users with access to the system on a a "first come, first served" basis.
Device Control Timeout
Local Operator Console, Remote Page Unit, or Remote Microphone) can remain in manual control of the NFC system.
Paging Timeout
Enter the maximum amount of time (30-300 seconds) that the microphone's PTT switch can be held.
54
Figure 3.4 NAC Options
Strobe Manufacturer
System Sensor
Wheelock
Gentex
Table 3.1 Maximum Number of Strobes by Manufacturer
If the Cooper Wheelock SP-SVC module is installed on TB23 of the main control board, allowing man-
Figure 3.5 Console Control
Enter the maximum amount of time (30-300 seconds) that one of the devices (Primary Operator Console,
Maximum Number of Strobes
31
34
26
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018