Riello RS5 Installation, Use And Maintenance Instructions page 23

Forced draught gas burner
Table of Contents

Advertisement

Available languages

Available languages

3.3 GAS TRAIN,
(as EN 676)
The gas train is supplied separately, for its adjustment see the enclosed instructions.
GAS TRAIN
TYPE
CODE
MBDLE 410 B01
3970549
MBDLE 412 B01
3970550
MBDLE 415 B01
3970558
3.4
GAS TRAIN ELECTRICITY SUPPLY
The gas train's power cables can be fed to the right or left
of the burner, as illustrated in figure 5.
Depending on the entry point, the cable clamp with pres-
sure test point (1) and simple cable clamp (2) may need
swapping over.
Consequently, you must make sure:
cable clamp (1) is positioned correctly;
the tube is positioned correctly so that there are no
restrictions likely to impede air flowing to the pressure
switch.
WARNING
If necessary, cut the tube to the right size.
3.5
GAS FEEDING LINE
Fig. 6
1
– Gas supply pipe
2
– Manual cock (charged to the installer)
3
– Gas pressure gauge (charged to the installer)
4
– Filter
5
– Gas pressure switch
6
– Safety valve
7
– Pressure governor
8
– Adjusting valve
M1 – Gas-supply pressure test point
M2 – Pressure coupling test point
20020956
CONNECTIONS
INLET
OUTLET
Rp 1 1 / 4
Flange 3
Rp 1 1 / 4
Flange 3
Rp 1 1 / 2
Flange 3
1
2
3
6
Natural gas  200kW and LPG 160
Natural gas  300 kW
Natural gas  300 kW
1
2
M1
4
5
6
7
GB
USE
330 kW
Fig. 5
2
D7113
1
8
M2
D5209

Advertisement

Table of Contents
loading

This manual is also suitable for:

20019993