Riello RS5 Installation, Use And Maintenance Instructions page 20

Forced draught gas burner
Table of Contents

Advertisement

Available languages

Available languages

2.
TECHNICAL DATA
2.1
TECHNICAL DATA
TYPE
Thermal power (1)
Natural gas (Family 2)
Electrical supply
Motor
Capacitor
Ignition transformer
Absorbed electrical power
(1) Reference conditions:
For gas family 3 (LPG) ask for separate kit.
COUNTRY
GAS CATEGORY
G20
H
GAS
G25
L
PRESSURE
G20
E
2.2
DIMENSIONS
503
278
300
225
216
20020956
920T2
160 – 330 kW
Net heat value: 8 – 12 kWh/Nm
Pressure: min. 20 mbar
Single phase, 230 V
Run current 1.9A
8 F
Primary 220-240V / 50/60 Hz – Secondary 15 kV - 25 mA
0.43 kW
Temp. 20°C - Barometric pressure 1013 mbar – Altitude 0 m above sea level.
AT - IT - DK - CH
GB - IE
II2H3B/P
II2H3P
20
25
150
203
-
137.600
283.800 kcal/h
3
= 7000 – 10,340 kcal/Nm
-
max. 100 mbar
~
±
10%
50Hz
-
2720 rpm
-
288 rad/s
DE
FR
II2ELL3B/P
II2Er3P
II2L3B/P
20
20
20 / 25
300
150
3
GB
3
NL
LU
BE
II2E3B/P
I2E(R)B, I3P
25
25
20 / 25
218
137
170
200
D4476

Advertisement

Table of Contents
loading

This manual is also suitable for:

20019993

Table of Contents