12.5 Compressor Reverse Rotation Protection Control

If the compressor is operating continuously for 5 minutes or longer and the temperature difference between
intake air and indoor heat exchanger is 2.5°C or less for continuous 2 minutes, compressor will stop and restart
automatically.
Time Delay Safety Control is activated before the compressor restart.
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
If this condition happens continuously for 5 times within 50 minutes, unit will turns off with POWER LED blinks.
The 5 times counter can be reset when either one of the following condition happen:
- Unit is OFF by remote control or AUTO OFF/ON button.
- Indoor intake temperature - indoor piping temperature >5°C for 1 minute or more.
The unit could be ON by pressing OFF/ON button at remote control but the POWER LED will continue blinking.
POWER LED blinking will reset if:
- Indoor intake temperature - indoor piping temperature >5°C for 1 minute or more.
- Power supply reset.