Restoring The Factory Settings - Siemens SIMATIC NET SCALANCE XP-200 Operating Instructions Manual

Industrial ethernet switches
Table of Contents

Advertisement

Upkeep and maintenance

7.2 Restoring the factory settings

7.2
Restoring the factory settings
NOTICE
Previous settings
If you reset, all the settings you have made will be overwritten by factory defaults.
NOTICE
Inadvertent reset
An inadvertent reset can cause disturbances and failures in the configured network with further
consequences.
With the "RESET" button
Restoring the factory settings during the startup phase
NOTICE
Reset despite disabled "RESET button"
Using the "RESET" button, you can always reset the device parameters to the factory settings
during the startup phase of the device. This also applies if the "Reset to Factory Defaults"
function was disabled in the configuration. This allows you to reset the device to the factory
defaults in an emergency.
If the function has been disabled with the configuration, it is only disabled on completion of the
startup phase.
When pressing the button, observe the information in the section "RESET button (Page 33)".
To reset the device to the factory defaults during the startup phase, follow the steps below:
1. Turn off the power to the device.
2. Loosen the screws of the cover.
3. Remove the cover.
4. Press the "RESET" button and reconnect the power supply to the device while holding down
the button.
5. Hold down the button until the red error LED "F" stops flashing after approximately 20
seconds and is permanently lit.
6. Release the button and wait until the fault LED "F" goes off.
The device starts automatically with the factory settings.
7. Close the cover (tightening torque 0.8 Nm), to ensure that the device is closed and water and
dust proof.
72
Operating Instructions, 03/2021, C79000-G8976-C428-08
SCALANCE XP-200