6.4 Connecting the drain piping

In this chapter

6.4.1 General guidelines

FTXTP25+35M5V1B_ATXTP25+35M5V1B
Daikin room air conditioner
4P519439-13N – 2021.03
2 Remove any burrs along the cut section using a half round needle file.
NOTICE
Do NOT use nippers to remove the pipe port cover, as this would damage the front
grille.
6.4.1

General guidelines..................................................................................................................................................

6.4.2

To connect the piping on right side, right-back, or right-bottom.........................................................................

6.4.3

To connect the piping on left side, left-back, or left-bottom................................................................................

6.4.4

To check for water leaks ........................................................................................................................................

Pipe length. Keep drain piping as short as possible.
Pipe size. If drain hose extension or embedded drain piping is required, use
appropriate parts that match the hose front end.
NOTICE
Install the drain hose with a downward slope.
Traps are NOT permitted.
Do NOT put the end of the hose in water.
6
Unit installation
|
27
28
29
30