Unit installation
e
a Recommended mounting plate fixing spots
b Pocket for the pipe port cover
c Tabs for placing a spirit level
d Through-the-wall hole Ø65 mm
6.3.2 To drill a wall hole
6.3.3 To remove the pipe port cover
Installer reference guide
26
a
b
117
211
d
a
a
48
162
337
CAUTION
For walls containing a metal frame or a metal board, use a wall embedded pipe and
wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
NOTICE
Be sure to seal the gaps around the pipes with sealing material (field supply), in order
to prevent water leakage.
1 Bore a 65 mm large feed-through hole in the wall with a downward slope
towards the outside.
2 Insert a wall embedded pipe into the hole.
3 Insert a wall cover into the wall pipe.
a b
c
a Wall embedded pipe
b Putty
c Wall hole cover
4 After completing wiring, refrigerant piping and drain piping, do NOT forget to
seal the gap with putty.
INFORMATION
To connect the piping on right-side, right-bottom, left-side or left-bottom, the pipe
port cover MUST be removed.
1 Cut off the pipe port cover from inside the front grille using a coping saw.
c
a
c
237
f
h
g
a
231
770
f Position for the tape measure at symbol " "
g Gas pipe end
h Liquid pipe end
e Drain hose position
a
116
d
A
e
a
171
48
337
(mm)
FTXTP25+35M5V1B_ATXTP25+35M5V1B
Daikin room air conditioner
4P519439-13N – 2021.03