6.4.5 To connect the electrical wiring to the indoor unit

Installer and user reference guide
36
Component
Recommended field fuse
Residual current device
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of
indoor unit for exact values).
NOTICE
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
For instructions on how to connect the decoration panel and the sensor kit, see
the installation manual delivered with the panel or the kit.
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
It is important to keep the power supply and the transmission wiring separated
from each other. In order to avoid any electrical interference the distance between
both wirings should ALWAYS be at least 50 mm.
NOTICE
Be sure to keep the power line and transmission line apart from each other.
Transmission wiring and power supply wiring may cross, but may NOT run parallel.
1 Remove the service cover.
2 User interface cable: Route the cable through the frame, connect the cable to
the terminal block (symbols P1, P2) and fix the cable with a tie wrap.
3 Transmission cable: Route the cable through the frame, connect the cable to
the terminal block (make sure the symbols F1, F2 match with the symbols on
the outdoor unit), and fix the cable with a tie wrap.
4 Power supply cable: Route the cable through the frame and connect the
cable to the terminal block (L, N, earth).
5 Divide the small sealing (accessory) and wrap it around the cables to prevent
water from entering the unit. Seal all gaps to prevent small animals from
entering the system.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
6 Reattach the service cover.
Class
20~40
50
63
6 A
Must comply with applicable legislation
80
100
125
FXFQ20~125BVEB
VRV system air conditioner
4P561452-1B – 2021.07

Hide quick links: