7 Configuration

7.1 Field setting

(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• C1: First code number
• C2: Second code number
: Default
FXFQ20~125BVEB
VRV system air conditioner
4P561452-1B – 2021.07
Make the following field settings so that they correspond with the actual
installation setup and with the needs of the user:
Ceiling height
Design decoration panel (if applicable)
Air flow direction
Air volume when thermostat control is OFF
Time to clean air filter
Setting: Ceiling height
This setting must correspond with the actual distance to the floor, capacity class
and air flow directions.
For 3-way and 4-way air flows (which require an optional blocking pad kit), see
the installation manual of the optional blocking pad kit.
For all-round air flow, use the table below.
If the distance to the floor is (m)
FXFQ20~63
≤2.7
2.7<x≤3.0
3.0<x≤3.5
Setting: Decoration panel type
When installing or changing the decoration panel type, ALWAYS check if the
correct values are set.
If the ... decoration panel is used
Standard or self-cleaning
Design
Setting: airflow direction
This setting must correspond with the actual used airflow directions. See the
installation manual of the optional blocking pad kit and the manual of the user
interface.
Default: 01 (= all-round air flow)
Example:
FXFQ80~125
≤3.2
13 (23)
3.2<x≤3.6
3.6<x≤4.2
M
13 (23)
7
Configuration
|
(1)
Then
M
C1
C2
0
01
02
03
(1)
Then
C1
C2
15
01
02
Installer and user reference guide
39