5.3.2 Refrigerant piping insulation

5.4 Preparing electrical wiring

5.4.1 About preparing electrical wiring

FXFQ20~125BVEB
VRV system air conditioner
4P561452-1B – 2021.07
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052  W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
Insulation thickness
Ambient temperature
≤30°C
>30°C
INFORMATION
Also read the precautions and requirements in the
4
precautions" [
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.
Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or
fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.
All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
Humidity
75% to 80% RH
≥80% RH
 5].
5
Preparation
|
Minimum thickness
15 mm
20 mm
"1  General safety
Installer and user reference guide
23