Alarms and Events
1.4.8
High Discharge Temperature
1
3
3
4
5
3–26
Alarm description (as shown on screen): Disc Temp High N.
Trigger: Discharge Temperature > High Discharge Temperature set point AND compressor is
running. Alarm cannot trigger if discharge temperature sensor fault is active.
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the Unit Controller keypad.
ESIE10-01
Part 3 – Troubleshooting