Decimal Point - Eaton Jockey XTJP O & M Manual

Pump controllers

Advertisement

O & M Manual IM05805023K
Effective: June 2012

4.1.3 DECIMAL POINT: (1000)

While holding the PGM button, press the UP Arrow button.
The display will show "dp"
Release the PGM button
The display will show "1000"
Do not change the setting.
4.1.4 OFFSET
Minimum Transducer Pressure: (0 psi)
While holding the PGM button, press the UP Arrow button.
The display will show "OF"
Release the PGM button
The display will show "+0000" – note: the "+" flashes
Do not change the setting.
4.1.5 FULL SCALE VALUE
While holding the PGM button, press the UP Arrow button.
The display will show "FS"
Release the UP Arrow and PGM buttons
The display will show "+0500" – note: the "+" flashes
Do not change the setting.
4.1.6 RELAY 1 – Hi ALARM SETPOINT: (+9999)
While holding the PGM button, press the UP Arrow button.
The display will show "1Hi"
Release the UP Arrow and PGM buttons
The display will show "+9999"
Do not change the setting.
4.1.7 RELAY 1 – Lo ALARM SETPOINT: (+0000) Pressure Start Point
While holding the PGM button, press the UP Arrow button.
The display will show "1Lo"
Release the UP Arrow and PGM buttons
The display will show "+0000"
Push the RIGHT Arrow button to move the value setting position
Set the desired START Point value using the UP and Down Arrow buttons
(eg: For 100psi, the display will show "+0100")
4.1.8 RELAY 2 – Hi ALARM SETPOINT
While holding the PGM button, press the UP Arrow button.
The display will show "2Hi"
Release the UP Arrow and PGM buttons
The display will show "+9999"
Do not change the setting.
Page 10
Maximum Transducer Pressure: (500 psi)
www.chfire.com
EATON XTJP / XTJY
Jockey Pump Controllers
PGM +
dp
1000
PGM +
OF
+0000
PGM +
FS
+0500
PGM +
1Hi
+9999
PGM +
1Lo
+0000
PGM +
2Hi
+9999
EATON CORPORATION