4. Digital Display

The XTJP and XTJY Jockey Pump Controllers are supplied standard with a
digital panel meter that indicates the current pressure and Stop and Start
pressure set points.
LED Display
High Visibility Red Superbright LED
Four full digits
0.56in (14mm) high characters
Flashing Alarms
Ratings
NEMA 4X
1/8 DIN
4.1 Programming
Ensure the Rotary Disconnect switch and the Hand-Off-Auto selector switch
are in the OFF position.
Apply power to the Jockey Pump Controller.
Once power is applied, turn the Rotary Disconnect switch to the ON position.
NOTE: The instructions below are based on the factory default settings.
Displayed values may vary depending on the programmed parameter setpoint
values. Factory default settings for each parameter are listed in Table 1.
4.1.1 Intial Setup
The Digital Display will show the current system pressure.
Press and hold the PGM button.
The display will show "run"
4.1.2 INPUT: (4.20)
While holding the PGM button, press the UP Arrow button.
The display will show "inP"
Release the PGM button
The display is factory set to "4.20".
If the display does not show "4.20", push the RIGHT Arrow button until "4.20" is
displayed