Pacific Power Source AMX Series Operation Manual page 21

Table of Contents

Advertisement

2.1.1 INPUT POWER REQUIREMENTS (cont.)
INPUT VOLTAGE AND INPUT CURRENT
The Model 360-AMX three phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
( cost option )
INPUT VOLTAGE AND INPUT CURRENT
The Model 390-AMX three phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
( cost option )
MODEL 360-AMX
INPUT CURRENT
(360-440 Hz optional)
1)
208 VAC ∆ ±10%, 47-63 Hz
2)
220 VAC ∆ ±10%, 47-63 Hz
3)
230 VAC ∆ ±10%, 47-63 Hz
4)
240 VAC ∆ ±10%, 47-63 Hz
5)
220/380 VAC ±10%, 47-63 Hz
6)
230/400 VAC ±10%, 47-63 Hz
7)
240/416 VAC ±10%, 47-63 Hz
8) 277/480 VAC ±10%, 47-63 Hz
MODEL 390-AMX
INPUT CURRENT
(360-440 Hz optional)
1)
208 VAC ∆ ±10%, 47-63 Hz
2)
220 VAC ∆ ±10%, 47-63 Hz
3)
230 VAC ∆ ±10%, 47-63 Hz
4)
240 VAC ∆ ±10%, 47-63 Hz
5)
220/380 VAC ±10%, 47-63 Hz
6)
230/400 VAC ±10%, 47-63 Hz
7)
240/416 VAC ±10%, 47-63 Hz
8) 277/480 VAC ±10%, 47-63 Hz
SECTION 2
INPUT
CURRENT
29 A
rms
27 A
rms
26 A
rms
25 A
rms
16 A
rms
15 A
rms
15 A
rms
14 A
rms
INPUT
CURRENT
46 A
rms
44 A
rms
42 A
rms
40 A
rms
26 A
rms
24 A
rms
24 A
rms
22 A
rms
13
SPECIFICATIONS
SERVICE
RECOMMENDED
40 A
40 A
40 A
40 A
20 A
20 A
20 A
20 A
SERVICE
RECOMMENDED
80 A
80 A
80 A
80 A
40 A
40 A
40 A
40 A