► Measure the total length L
(± 0�1 inch) (→ 6.3.1 and → 6.3.2)�
► Deduct 9 mm from the measured value� L = L
► Round up the determined value (step increment 0�5 cm / 0�2 inch)�
► Select [LEnG] and set the determined value L
(setting range: 10�0 ��� 160�0 cm / 4�0 ��� 63�0 inch)�
10.5.9 Adjustment to the medium to be detected
In case of doubt, carry out an application test to make sure that the setting
which is best for the medium to be measured is used!
► Select [MEdI] and set the value:
- [HIGH] for water and water-based media�
- [LOW] for oils and oil-based media�
10.6 Changing the password
The password protects all parameters from unauthorised change� If the
password protection is activated, the parameters can still be read, only the
write access is blocked�
Password on delivery: Not activated!
If the password is lost, changing the parameters is no longer possible� In
this case, the unit needs to be sent back to the manufacturer!
► Select [CodE] and enter a new password (4-digit number between 1000
and 9999)�
► Keep the password in a safe place!
► To deactivate the password protection select the value [nonE]; to do so,
a full cycle of all values is necessary�
10.7 Enter password [KEy.C]
Only visible if the password protection is activated�The parameter is
displayed immediately after opening the user menu�
► Select [KEy�C] and enter the correct password�
> When the correct password is entered, there is full write and
read access to all operating parameters of the unit�
> When a wrong password is entered, [FAIL] is displayed and
there is only read access�
of the coaxial probe to a precision of ± 2 mm
K
K
- 9 mm�
LEnG
UK
MEdl
CodE
KEy.C
27