FXDQ-SPV1
Model
Power supply
1 3 Cooling capacity
2 3 Heating capacity
Cooling
Power input
Heating
Casing / Colour
Dimensions: (H×W×D)
Type
Motor output ×
Number of units
Airflow rate
Fan
(HH/H/L)
4 External static
pressure
Drive
Temperature control
Sound absorbing thermal insulation material
Air filter
Liquid pipes
Piping
Gas pipes
connections
Drain pipe
Mass
6 7 8 Sound pressure level
(HH/H/L)
Safety devices
Refrigerant control
Standard accessories
Specification
Drawing No.
Sound level
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 5 m, level difference: 0 m.
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. External static pressure is changeable to set by the remote controller. This pressure means "High static pressure -
Standard". (Factory setting is 10 Pa for FXDQ20-32SP models and 20 Pa for FXDQ40-63SP models.)
5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
7. Values are based on the following conditions: FXDQ20-32SP: external static pressure of 10 Pa; FXDQ40-63SP:
external static pressure of 20 Pa.
8. The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-
suction operation can be obtained by adding 5 dB(A).
FXDQ50SPV1
1 phase, 220-240 V, 50 Hz
kcal/h
4,800
Btu/h
19,100
kW
kcal/h
5,400
Btu/h
21,500
kW
kW
0.180
kW
0.152
Galvanized steel plate
mm
200×900×450
Sirocco fan
W
130×1
m³/min
15.0/13.0/10.5
l/s
250/217/175
cfm
530/459/371
Pa
50-20
Direct drive
Microprocessor thermostat
for cooling and heating
Foamed polyethylene
— 5
mm
φ6.4 (Flare connection)
mm
φ12.7 (Flare connection)
VP20
mm
(External dia. 26, Internal dia. 20)
kg
dB(A)
35/33/31
Fuse, Thermal protector for fan motor
Electronic expansion valve
Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers,
Insulation for fitting, Metal clamp, Washer fixing
plate, Screws for duct flanges
C: 3D090326A
C: 4D090510A
5.6
6.3
20
Operation manual, Installation manual, Drain
Insulation for fitting, Metal clamp, Washer fixing
5
EDTFVN391825
FXDQ63SPV1
1 phase, 220-240 V, 50 Hz
6,100
24,200
7.1
6,900
27,300
8.0
0.196
0.168
Galvanized steel plate
200×1,100×450
Sirocco fan
130×1
20.0/16.0/12.5
333/267/208
706/565/441
40-20
Direct drive
Microprocessor thermostat
for cooling and heating
Foamed polyethylene
— 5
φ9.5 (Flare connection)
φ15.9 (Flare connection)
VP20
(External dia. 26, Internal dia. 20)
23
37/35/33
Fuse, Thermal protector for fan motor
Electronic expansion valve
hose, Sealing pads, Clamps, Washers,
plate, Screws for duct flanges
C: 3D090326A
C: 4D090511A
Conversion formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
l/s=m³/min×1000/60