MOUNTING THE EVAPORATOR UNITS
It is vital that the units be set apart and oriented so that the return air
from one unit does not recirculate into the supply air of the other unit.
NOTE: If installing the units without attic access, perform steps 5-21 prior to steps 3-4.
3.
Secure the mounting bracket to the primary evaporator unit using the twelve (12) supplied 3/8" Phillips pan-head
screws.
NOTE: You are REQUIRED to use only the mounting locations provided. These locations
ensure that the installer will not drill into any copper or electrical wiring within the system.
4.
Secure the primary evaporator unit's mounting bracket to the opening using the twelve (12) supplied 21/2" Phillips-
head screws.
Display, Power. and
Thermostat Wires
Line Set / Drain Line
Page 13
08/04/21
Routed Items:
1. Display cable
2. Power and thermostat wires
3. Drain line
4. Line set