Example of ConfigureCmd
Cmd
Description
Device
ID
Config
0x01
ReportReq
Config
0x81
ReportRsp
R718IJK
ReadConfig
0x02
ReportReq
ReadConfig
0x82
ReportRsp
(1) Configure R718IJK device parameter
MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v,
Downlink: 015C003C003C0100640200
Device Return:
815C000000000000000000 (configuration success)
815C010000000000000000 (configuration failure)
(2) Read R718IJK device parameter
Downlink: 025C000000000000000000
Device Return: 825C003C003C0100640200 (device current parameter)
Example for MinTime/MaxTime logic:
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime
Sleeping(MinTime)
Wakes up and collects data
REPORTS 3.6V
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange value.
Device
Type
MinTime
MaxTime
(2bytes Unit: s)
(2bytes Unit: s)
(0x00_success)
0x5C
MinTime
MaxTime
(2bytes Unit: s)
(2bytes Unit: s)
Wakes up and collects data
REPORTS 3.6V
NetvoxPayLoadData
BatteryChange
(1byte Unit:0.1v)
Status
Reserved
(9Bytes, Fixed 0x00)
ADCRawValue
BatteryChange
(1byte
Unit: 0.1v)
ADC Raw Value Change=100mV, Current Change =2mA
MaxTime
Sleeping(MinTime)
Wake up and collects data
6
ADCRawValue
CurrentChange
Change
(1byte Unit:
(2byte Unit:
1mA)
1mV)
Reserved
(8Bytes, Fixed 0x00)
CurrentChange
Change
(1byte Unit:
(2byte Unit:
1mA)
1mV)
REPORTS 3.6V
Reserved
(4Bytes,
Fixed0x00)
Reserved
(4Bytes, Fixed
0x00)

Advertisement

Table of Contents
loading