Wireless 2-gang thermocouple sensor for k/t/n type

Advertisement

Quick Links

R718CK2 / R718CT2 / R718CN2
Wireless 2-Gang Thermocouple Sensor for K/T/N Type
Wireless 2-Gang Thermocouple Sensor
for
K/T/N Type
R718CK2/CT2/CN2
User Manual
Copyright©Netvox Technology Co., Ltd.
This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained
in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX
Technology. The specifications are subject to change without prior notice.

Advertisement

Table of Contents
loading

Summary of Contents for netvox R718CN2

  • Page 1 This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The specifications are subject to change without prior notice.
  • Page 2: Table Of Contents

    Table of Content 1. Introduction ....................................... 2 2. Appearance ......................................3 3. Main Features ....................................3 4. Set up Instruction ....................................4 5. Data Report ....................................... 5 5.1 Example of ReportDataCmd ..............................5 5.2 Example of ConfigureCmd ............................... 7 5.3 Example for MinTime/MaxTime logic............................. 8 6.
  • Page 3: Introduction

    Its use temperature is -40 ~ +125℃, it is used in the temperature range of -40~0℃, and the stability is better. R718CN2 (nickel-chromium-silicon-nickel-silicon-magnesium thermocouple): Its use temperature is -40 °C~ +800°C, the N-type thermocouple has good linearity, large thermoelectromotive force, high sensitivity, and good stability and uniformity.
  • Page 4: Appearance

     Applicable to third-party platforms: Actility/ThingPark, TTN, MyDevices/Cayenne  Low power consumption, longer battery life support: Battery life is determined by sensor reporting frequency and other variables, please refer to http://www.netvox.com.tw/electric/electric_calc.html On the website, users can find battery life of various models in different configurations.
  • Page 5: Set Up Instruction

    4. Set up Instruction On/Off Power on Insert batteries. (User may need a screwdriver to open) Turn on Press and hold the function key for 3 seconds till the green indicator flashes once. Turn off (Restore to factory setting) Press and hold the function key for 5 seconds till green indicator flashes for 20 times. Power off Remove Batteries.
  • Page 6: Data Report

    Note: (1) The real data sending cycle will be programmed before shipment. (2) The interval between two reports must be the minimum time Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver http://cmddoc.netvoxcloud.com/cmddoc to resolve uplink data.
  • Page 7 Temperature2 Reserved R718CT2 0x17 0x01 (1Byte, unit:0.1V) (Signed2Bytes,unit:0.1°C) (Signed2Bytes,unit:0.1°C) (3Bytes,fixed 0x00) R718CN2 0x18 Example 1 of Uplink: 0116012400FD0109000000 byte (01): Version byte (16): DeviceType 0x16-R718CK2 byte (01): ReportType byte (24): Battery, 24H =36 D , 36x0.1v = 3.6v byte (00FD): Temperature1, 00FD H =253 D , 253x0.1°C = 25.3°C...
  • Page 8: Example Of Configurecmd

    (2bytes Unit:s) (1byte Unit:0.1v) (2Bytes,Fixed 0x00) ConfigReport Status Reserved 0x81 R718CK2 0x16 (0x00_success) (8Bytes,Fixed 0x00) R718CT2 0x17 ReadConfig Reserved R718CN2 0x02 0x18 (9Bytes,Fixed 0x00) ReportReq ReadConfig MinTime MaxTime BatteryChange TemperatureChange Reserved 0x82 (2byte Unit:0.1℃) (2bytes Unit:s) (2bytes Unit:s) (1byte Unit:0.1v)
  • Page 9: Example For Mintime/Maxtime Logic

    5.3 Example for MinTime/MaxTime logic Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V MaxTime MaxTime Sleeping(MinTime) Sleeping(MinTime) Wake up and collects data Wakes up and collects data Wakes up and collects data REPORTS 3.6V REPORTS 3.6V REPORTS 3.6V Note: MaxTime=MinTime.
  • Page 10: Installation

    3) We do not recommend to set the MinTime Interval value too low. If the MinTime Interval is too low, the device wakes up frequently and the battery will be drained soon. 4) Whenever the device sends a report, no matter resulting from data variation, button pushed or MaxTime interval, another cycle of MinTime/MaxTime calculation is started.
  • Page 11: Information About Battery Passivation

    7. Information about Battery Passivation Many of Netvox devices are powered by 3.6V ER14505 Li-SOCl2 (lithium-thionyl chloride) batteries that offer many advantages including low self-discharge rate and high energy density. However, primary lithium batteries like Li-SOCl2 batteries will form a passivation layer as a reaction between the lithium anode and thionyl chloride if they are in storage for a long time or if the storage temperature is too high.
  • Page 12: Important Maintenance Instruction

    8. Important Maintenance Instruction Kindly pay attention to the following in order to achieve the best maintenance of the product: • Keep the device dry. Rain, moisture, or any liquid might contain minerals and thus corrode electronic circuits. If the device gets wet, please dry it completely.