Hydraulic System - Riello PRESS 1G Installation, Use And Maintenance Instructions

Pressure jet burner
Table of Contents

Advertisement

HYDRAULIC SYSTEM

Gravity feed from the bottom of the oil storage tank
Gravity feed over the top of the oil storage tank
Suction feed
H = Difference in height;
The copper pipes of 10 mm and 12 mm I.D., as shown on the tables above, may be replaced by steel pipes of 3/8"
or 1/2" Gas.
5901
The dimension P should not exceed 10 m, to avoid
breakage of pump seals.
The dimension P should not exceed 10 m, to avoid
breakage of pump seals.
Oil lines must be perfectly sealed. The use of copper
pipe is therefore recommended. The pump suction
must not exceed 4 m w.c. (30 cm Hg) because beyond
this value the pump becomes noisy.
The return line must terminate at the same level as the
foot valve; otherwise the pump may become air-locked.
L = The total length of the suction line, including the vertical section.
3
H
meters
I.D. 8 mm
0.5
4
1
8
1.5
12
2
16
2.5
20
H
meters
I.D. 10 mm
0
40
0.5
36
1
32
2
24
3
15
3.5
10
L meters
I.D. 10 mm
10
20
30
40
50
L meters
I.D. 12 mm
100
90
80
58
36
25

Advertisement