Securing The Burner To The Boiler; Combustion Head Adjustment - Riello RG1RKD Installation, Use And Maintenance Instructions

Light oil burner
Table of Contents

Advertisement

Available languages

Available languages

5.6

Securing the burner to the boiler

Provide an adequate lifting system of the burner.
With some boilers it is possible that the CO values
exceed those stated in this manual. To lower
these emissions it is necessary to use the recircu-
lating pipe supplied.
WARNING
To install the burner on the boiler, do the following:
 Insert on the flange 1)(Fig. 8) the screw and the two nuts
3)(Fig. 8).
 If necessary, widen the holes 6)(Fig. 7) of the insulating gas-
ket 5)(Fig. 8).
 To the door of the boiler 4)(Fig. 8) fix the flange 1) using the
screws 2) and (if necessary) the nuts 3) placing the insulat-
ing gasket 5)(Fig. 8) in-between.
5.7

Combustion head adjustment

The adjustment of the combustion head varies depending on the
burner output. Do the following to adjust it:
 turn the adjustment screw 12)(Fig. 9) clockwise or anti-
clockwise until the notch on the regulating rod 8)(Fig. 9) lines
up with the outer surface of the nozzle-holder assembly
7)(Fig. 9).
 In the example the head is set for an output of 0.85 GPH at
15 bar.
The regulating rod 8)(Fig. 9) is calibrated to notch 3 coincid-
ing with the outer surface of the nozzle-holder assembly
7)(Fig. 9) as shown in Tab. G page 21.
20138077
Installation
In any event, make sure that the combustion head
crosses the entire thickness of the boiler door.
WARNING
The seal between burner and boiler must be
airtight.
WARNING
S9673
14
GB
6
D5012
S7189
Fig. 7
Fig. 8
12
7
8
Fig. 9

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

3736654

Table of Contents