Quick Start Guide
3.6
Grounding
Always ground the housing in accordance with national and local
electrical codes.
3.6.1
Grounding using the cable shield
Make sure the instrument cable shield is:
•
Trimmed close and insulated from touching the level switch housing.
•
Continuously connected throughout the segment.
•
Connected to a good earth ground at the power supply end.
Figure 3-7: Signal Cable Shield Grounding at Power Supply End
A. Trim shield and insulate
B. Minimize distance
C. Trim shield
D. Connect shield back to the power supply ground