Burner Adjustment; Optimum Calibration Values - Riello RX 500 S/PV Modulating Operation

Premix gas burner
Table of Contents

Advertisement

6.6

Burner adjustment

The optimum adjustment of the burner requires an analysis of
flue gases at the generator outlet.
The burner application at the generator, the adjustment and the
testing must be carried out in compliance with the instruction
manual of the generator itself, including the control of the concen-
tration of CO and CO
in the flue gases and of their temperature.
2
Check in sequence:
max output
min output
Output upon ignition
The MAX output should be equal to the value requested by the
boiler used. To increase or decrease its value use the external
modulation control.
Measure the gas delivery on the counter to precisely establish the
burnt output.
Using a smoke analyser, measure the value of the CO
in order to optimise the burner calibration.
The correct values are shown in Tab. R.
To correct these values act on the gas valve in the following way:
 to increase the gas delivery and the CO
towards the "+" sign (Fig. 25);
 to reduce the gas delivery and the CO
towards the "-" sign (Fig. 25);.
The MIN output should be equal to the value requested by the
boiler used. To increase or decrease its value use the external
modulation control.
Measure the gas delivery on the counter to precisely establish the
burnt output (to be corrected in relation to the pressure of the
gas).
Using a smoke analyser, measure the value of the CO
in order to optimise the burner calibration.
The correct values are shown in Tab. R.
To correct these values act on the gas valve in the following way:
 to increase the gas delivery and the CO
towards the "+" sign (Fig. 25);
 to reduce the gas delivery and the CO
towards the "-" sign (Fig. 25);.
The IGNITION output can be obtained in area A highlighted in
the charts on page 12. To raise or lower its value, adjust the pa-
rameter P0) using the control panel of the control box (Fig. 8 on
page 15).
Do not modify the adjustments of the gas
valve for the ignition output!
WARNING
20138630
Start-up, calibration and operation of the burner
or the O
2
: turn the V1 screw
2
: turn the V1 screw
2
or the O
2
: turn the V2 screw
2
: turn the V2 screw
2
6.6.1

Optimum calibration values

MIN output
CO
(%)
2
Methane
8
LPG
9.5
G25
7.8
2
D9714
2
20146400
Minimum gas flow
adjustment on the stabiliser (V2)
32
GB
MAX output
O
(%)
CO
(%)
O
2
2
6.6
8.5
6.4
10
6.8
8.3
Adjustment of maximum gas flow (V1)
(%)
2
5.7
5.6
5.8
Tab. R
Fig. 24
Fig. 25