Product Description; Technical Data - Sonnen sonnenBatterie eco 8.0/2,5 Operating Instructions Manual

For operators
Table of Contents

Advertisement

3 Product description

3.1 Technical data

sonnenBatterie eco
System data (AC)
Nominal voltage
Nominal frequency
Nominal power
Nominal current
Power factor range
Current (Max. continous)
Max. output fault current
Inrush current
Mains connection
Max. ext. overcurrent protection
Mains topology
Mains connection fuse
Battery data (DC)
Cell technology
Nominal capacity
Usable capacity
Nominal voltage
Current (Max. continous)
Short-circuit current(I
)
SC
Min. number of battery modules
Max. number of battery modules
Dimensions / weight without extension cabinet (from 2.5 up to 5 kWh)
Dimensions (H/W/D) in cm
Weight in kg
Dimensions / weight with small extension cabinet (from 2.5 up to 10 kWh)
Dimensions (H/W/D) in cm
Weight in kg
Dimensions / weight with big extension cabinet (from 2.5 up to 15 kWh)
Dimensions (H/W/D) in cm
Weight in kg
Safety
Protection class
Required fault current monitoring
KD-436 | 22283 | EN | 04
8.0/2,5
8.0/5
1,100 W
2,500 W
1.6 A
3.6 A
Miniature circuit breaker | Type B | 10 - 16 A
2.5 kWh
5.0 kWh
2.25 kWh
4.5 kWh
88/67/23
58
81
137/67/23
74
97
85
108
In TT networks: Residual current device (RCD) with a rated differential current of
300 mA; requirements on site must be observed.
8.0/7,5
8.0/10
400 V
50 Hz
3,300 W
3,300 W
4.8 A
4.8 A
0.9 capacitive ... 0.9 inductive
4.8 A
120 mA
0 A
three-phase, L1 / L2 / L3 / N / PE
16 A, 3ph
TN / TT
lithium iron phosphate (LiFePO4)
7.5 kWh
10.0 kWh
6.75 kWh
9.0 kWh
48 V
75 A
90 A
1
6
-
-
-
-
120
143
186/67/23
131
154
I / PE conductor
Product description | 3
8.0/12,5
8.0/15
3,300 W
3,300 W
4.8 A
4.8 A
12.5 kWh
15.0 kWh
11.25 kWh
13.5 kWh
-
-
-
-
-
-
-
-
177
200
9 / 36

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents