FPS-T1U RACK SAFETY INSTRUCTIONS
SAFETY APPROVALS
UL62368-1 and CSA22.2 No.62368-1 - CTUVus
IEC 62368-1 - CB Test Report and Certificate.
EN 62368-1 - TUV Mark, CE Mark.
Marking by the CE Symbol indicates compliance to the EMC Directive, the Low Voltage Directive and RoHS Directive of the
European Union.
A "Declaration of Conformity" in accordance with the preceding directives and standards has been made and is on file at our
EU representative: TDK-Lambda Germany GmbH, Karl-Bold-Str. 40, D-77855 Achern.
A "Declaration of Conformity" may be accessed via company website www.emea.tdk-lambda.com/manual
SAFETY INSTRUCTIONS
CAUTION: The following safety precaution must be observed during all phases of operation, service and repair of this
equipment. Failure to comply with the safety precautions or warnings in this document violates safety standards of design,
manufacture and intended use of this equipment and may impair the built-in protections within. TDK Lambda shall not be
liable for user's failure to comply with these requirements.
CAUTION:
FPS-T1U units are not authorized for use as critical component in nuclear control systems, life support systems or
equipment for use in hazardous environments without the express written approval of the managing director of TDK-Lambda.
INSTALLATION (OVERVOLTAGE) CATEGORY& ENVIRONMENTAL CONDITIONS
The FPS-T1U units have been evaluated to Overvoltage category II.
The FPS-T1U units intended for use in the following operation conditions:
* Indoor use
* Pollution degree 2
* Max. operational altitude: 3000m above sea level
*Ambient temperature: -10°C-50°C at 100% load, up to 70°C with output de-rating applied (See Specification)
GROUNDING
FPS-T1U units are Class I product. To minimize electrical shock hazard, the FPS-T1U units must be connected to an electrical
ground. The instruments must be connected to the AC power supply mains through a three conductor power cable, with the
ground wire firmly connected to an electrical ground (safety ground) at the power outlet. For instruments designed to be hard-
wired to the supply mains, the protective earth terminal must be connected to the safety electrical ground before any other
connection is made. Any interruption of the protective ground conductor or disconnection of the protective earth terminal will
cause a potential shock hazard that might cause personal injury.
The ground cable connected to the permanent connection must meet the Dimensions of the wires: FPS-T1Uxy followed by /
TB-8AWG.
LIVE CIRCUITS
Operating personnel must not remove the FPS-T1U units cover.
No internal adjustment or component replacement is allowed by non-TDK Lambda qualified service personnel. Never replace
components with power cable connected. To avoid injuries, always disconnect power, discharge circuits and remove external
voltage sources before touching components.
23