9. OEM INSTALLER SETTINGS

RETURN TO
NORMAL MODE
STEP 1I – From normal mode, press UP and NEXT
STEP 1I
simultaneously for about 3 seconds and release.
STEP 2I – Inlet Water Hardness (PPM) - Set the amount
STEP 2I
of infl uent hardness using UP or DOWN. Press NEXT
to go to Step 3I. Press REGEN to exit OEM Installer
Settings.
This screen will only be displayed when "rES" is selected
in step 3S.
STEP 3I – Service Water Hardness (PPM) - If a mixing
STEP 3I
valve is installed in the valve, service hardness needs to
be set. Setting range is always less than the setting in
Step 2I. This screen will only be displayed when 'rES' is
selected in Step 3S.
Press NEXT to go to Step 4I. Press REGEN to return to
previous step.
STEP 4I – Day Override - Adjust day override from 1 - 28
STEP 4I
days or OFF using UP or DOWN. Press NEXT to go to
Step 5I. Press REGEN to return to previous step.
STEP 5I – Time of Regeneration, Hour - Set the time
STEP 5I
(hour) for regeneration using UP or DOWN. The default
time is 2:00 a.m. This display will show "on 0" if "on 0" is
selected in Step 3S. Press NEXT to go to Step 6I. Press
REGEN to return to previous step.
STEP 6I – Time of Regeneration, Minutes - Set the time
STEP 6I
(minutes) for regeneration using UP or DOWN. The
default time is 2:00 a.m. This display will not appear if
"on 0" is selected in Step 3S. Press NEXT to exit Installer
Settings. Press REGEN to return to previous step.
13