Mercury 310 Automated Gate System
5.1.2
Wire Run Sizing
Use the table below to determine high voltage wire size requirements.
Distance shown in the chart is measured from the operator to the power source.
'
If power wiring is greater than the maximum distance shown, a service feeder is recommended.
'
When large gauge wire is used, a separate junction box must be installed for the operator connection.
'
Wire table is based on stranded copper wire. Wire run calculations are based on a 120 VAC power
'
source with a 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow
for other electrical losses in the system.
120V/AWG GAUGE
MAX RUN
Mercury 310 controller accepts low voltage (<24VDC) power only.
5.1.3
Power Supply Wiring
Access the power supply by opening the front cover, then pulling open the controller panel from the magnet.
Front Cover
Open
Controller
Panel Open
Mercury 310
Controller
www.ApolloGateOpeners.com | (800) 878-7829 | Sales@ApolloGateOpeners.com
Installation and Programming Manual
Maximum Run Per Wire Gauge
14
180 FT
(54.8m)
WARNING
Power Supply Module Location
12
10
8
280 FT
460 FT
700 FT
(85.3m)
(140m)
(213.3m)
6
4
1150 FT
1800 FT
(350.5m)
(548.6m)
Transformer
Panel
Magnet
Power Supply
Module
AC Power
Conduit
to Power
Supply