Technical description of the burner

4.1

Technical data

MODEL
CODE
OUTPUT
(1)
DELIVERY
(1)
FUEL
- Net calorific value
- Density
- Viscosity at 20 °C
OPERATION
PUMP J7C
delivery (at 12 bar) pressure range fuel
temperature
NOZZLES
STANDARD APPLICATIONS
AMBIENT TEMPERATURE
COMBUSTION AIR TEMPERATURE
NOISE LEVELS
(2)
Reference conditions: Ambient temperature 20 °C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(1)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated
(2)
output. The sound power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category 3"
measuring accuracy, as set out in EN ISO 3746.
4.2

Electrical data

Motor IE2
CODE
POWER SUPPLY
ELECTRICAL MOTOR
Operating current
Acceleration current
IGNITION TRASFORMER
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
4.2.1

Accessories (optional):

RADIO DISTURBANCEPROTECTION KIT
If the burner is installed in places particularly subject to
radio disturbance (emission of signals exceeding 10 V/m)
owing to the presence of an INVERTER, or in applications
where the length of the thermostat connections exceeds 20
metres, a protection kit is available as an interface between
the control box and the burner.
BURNER
Code
2916074
Technical description of the burner
2nd stage
kW
Mcal/h
kg/h
1st stage
kW
Mcal/h
kg/h
kWh/kg
Mcal/kg
kg/dm
mm
2
/s max
kg/h
bar
° C max
number
°C
°C max
Sound pressure
dBA
Sound power
V
Hz
rpm
W
V
A
A
V1 - V2
I1 - I2
W max
RL 190
3010386
3475613
3
Intermittent (min. 1 stop in 24 hours).
Two-stage (high and low flame) and single-stage (all - nothing).
Boilers: water, steam, diathermic oil
3475613
400 with neutral ~ +/- 10%
50 - three-phase
2900
4500
400
8.7
81
4.2.2

Variants

Model
RL 190
RL 190
6
GB
RL 190
20011008
1423 - 2443
1224 - 2100
120 - 206
759 - 1423
653 - 1224
64 - 120
LIGHT OIL
11.8
10.2 (10.200 kcal/kg)
0.82 - 0.85
6 (1.5 °E - 6 cSt)
230
10 - 21
90
2
0 - 40
60
83.9
94.9
20011008
230 with neutral ~ +/- 10%
50 - three-phase
2900
4500
230
141
230 V - 2 x 5 kV
1.9 A - 35 mA
5500
IP 44
Power supply
Code
3475613
20011008
15
electrical
400 V
230 V