GAS BURNER
General introduction of the PCH
Premix burner (venturi, gas fan, pilot group, head) gas valve
GAS BURNER
Electronic controls with display
Combustion chamber in stainless steel AISI 430 (AISI 441 in the next future)
Exchanger bundle in stainless steel AISI 441
Safety thermostat (and additional probe)
PCH working cycle
Heat is required
Burner fan starts to pre-wash combustion chamber EV1 and EVP gas valves open to gas feed pilot burner
Start up electrode gives ignition sparks on pilot burner
EV2 main gas valve opens to gas feed main burner
Combustion starts thanks to pilot flame ignition
The electronic boards close EVP and stops the pilot
Air fans
ON delay ≤ 60'' after the burner ON
OFF delay ≥ 180'' after the burner OFF
Possible safety devices of the fans must be connected in series with the burner (ID1/IDC on terminal CN08)
STB and temperature probe
Safety Thermostat STB: it stops the burner at 100°C (manual reset required by Gas Directive)
NTC temperature probe: it forces the burner to modulate (factory set of ST1 = 45°C) or to stop (f.s. of TH1=60) before the STB,
automatic reset as soon as the air temperature decreases. Fault F51 recorded.