Electrical Heater - Lennox eNeRGy Series Installation, Operating And Maintenance

High efficiency packaged air treatment unit
Table of Contents

Advertisement

ELECTRICAL HEATER

WARNING: electrical heater is connected to main power – risk of electrical shock – switch off the unit prior
GAS BURNER
to open this section
The electrical heaters are placed after the coil.
It is protected as standard against overheat via a high temperature overload protection.
There are three sizes available for each size of unit:
S: Standard heat
M: Medium heat
H: High heat
Unit
Description
E014- E019
Unit
Description
E22- E27
eNeRGy-IOM-2020.11-EN
Type of modulation
Standard
Medium
High
Type of modulation
Standard
Medium
High
1 stage
Triac
Triac
1 stage
Triac
Triac
Capacity
36 kW
90 kW
108 kW
Capacity
54 kW
108 kW
144 kW
Current
52 A
129,9 A
155,9 A
Current
77,9 A
155,9 A
207,8 A