Siemens SIMOVERT MASTERDRIVES 6SE70 C.87-2DA0 Series Operating Instructions Manual page 56

Braking unit
Table of Contents

Advertisement

Available languages

Available languages

Start-up
Braking Unit
6SE70__-_C.87-2DA0
6SE70__-_E.87-2DA0
6SE70__-_F.87-2DA0
6SE70__-_H.87-2DA0
6-2
The voltage limit switch is located behind the front cover.
Rated Voltage
208 V to 230 V
380 V to 460 V
380 V to 400 V
500 V to 575 V
500 V
660 V to 690 V
660 V
Table 6-1
Setting of the voltage limit switch
Set parameters on converter: (see section headed "Parameterization"
in operating manual for SIMOVERT MASTERDRIVES)
♦ P515, Vdmax controller, set parameter value to "0".
♦ If the braking unit is to report a fault to the SIMOVERT
MASTERDRIVES, "Ext Fault 2" must be used ;
e.g. P586 "Src No ext Fault 2"external 2" = 10...22
(binary inputs 1 to 7).
Unità di frenatura / Braking Unit
Voltage Limit
387 V
774 V (factory setting)
673 V
967 V (factory setting)
841 V
1158 V (factory setting)
1070 V
6SE7087-2CX87-2DA0
03.2004
Switch position
fixed, cannot be
changed
1
2
1
2
1
2
1
2
1
2
1
2
Siemens AG
SIMOVERT MASTERDRIVES

Advertisement

Chapters

Table of Contents
loading

Table of Contents