Product Description - Siemens SIMOVERT MASTERDRIVES 6SE70 C.87-2DA0 Series Operating Instructions Manual

Braking unit
Table of Contents

Advertisement

Available languages

Available languages

03.2004
2

Product Description

Siemens AG
6SE7087-2CX87-2DA0
SIMOVERT MASTERDRIVES
Electric energy is fed into SIMOVERT MASTERDRIVES when a motor
is decelerated. In order to prevent overvoltage tripping, a braking
resistor is used to convert this energy into heat. This resistor may be a
part of the braking unit or it is connected to it.
The braking unit is connected to the DC bus terminals of the drive.
When the DC bus voltage reaches a pre-defined limit, the braking unit
automatically turns on and prevents the DC bus voltage from continuing
to increase.
The braking unit operates autonomously. The power supply of the
electronics is integrated in the unit.
The braking unit is available in three frame sizes.
♦ frame size S,
5 kW to 10 kW:
integrated braking resistor:
external braking resistor:
♦ frame size A,
10 kW to 20 kW:
integrated braking resistor:
external braking resistor:
50 kW:
external braking resistor
♦ frame size B,
100 kW to 200 kW:
external braking resistor
Unità di frenatura / Braking Unit
Product Description
for short braking operation
if the integrated braking resistor is
not sufficient
for short braking operation
if the integrated braking resistor is
not sufficient