Fcpm082A10 Electrical Specifications; Fcpm082010 Connections - Carel FCP/1 User Manual

Regulator with microprocessor control
Hide thumbs Also See for FCP/1:
Table of Contents

Advertisement

10.2

FCPM082A10 electrical specifications

Power supply
Analogue outputs
Inputs
Signal lights
Terminals and connectors
Operating conditions
Storage conditions
Index of protection
Environmental pollution
Protection against electric shock
PTI of the insulating materials
Period of stress across the insulating parts
Type of action –disconnection
Category of resistance to heat and fire
Immunity against voltage surges
Ageing characteristics
No. of automatic operating cycles
Software class and structure
Case
Dimensions
Assembly
Certification
10.3

FCPM082010 connections

L, N
Controller 230 Vac power supply input
L1, N
Power supply output to 0 to 230 Vac load
ID1, GND
Programmable digital input. Motor protector or second set point management, see dipswitch
configuration.
B1, GND, +5V
Analogue input for pressure (ratiometric) or temperature reading (CAREL NTC probe or 0/10 V
control) in circuit 1
B2, GND, +5V
Analogue input for pressure (ratiometric) or temperature reading (CAREL NTC probe) in circuit 2
NTC input for temperature reading used in the feed-forward algorithm (CAREL NTC probe)..
B3, GND
RS485 serial with CAREL supervisor or ModBus slave protocol (the FCSER0000 option is required).
GNX, RX+TX+,
RX-TX-
Y1, GND
Control output for expansion with auxiliary power device;
Code +030220391 – rel 1.1 07/11/06
230 Vac single-phase. -15% +10% 50/60 Hz
1 phase control 0-230Vac single-phase, 8A (min 500mA)
1 phase control function
0-5V 2mA max;
Green power LED
Power supply and analogue outputs:
Screw terminals for cable cross-section min. 2.5 mm
Signals:
Spring terminals for cable cross-section max 2.5mm
-20/+50°C, <85% rH non-condensing
-20/+70°C, <85% rH non-condensing
IP54
230 V~
2
max 4 mm
2
.
2
.
2
Class I
250V
Long
1Y
Category D (UL94 – V0)
Category II
60,000 operating hours
100,000
Class A
Metallic (Al) with plastic cover (ball pressure test 75°C)
140x135x90 mm
Metal case fastened to panel or wall mounted using 4 screws dia. 3.5/4 mm
EMC :EN 61326-1, EN 55014-1, EN 55014-2
Safety: EN 60730-1
PROG.
KEY
Fig. 10.a
37
FCP manual
Table 10.b

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcpm082010Fcpm082a10

Table of Contents