Specifications And Connections; Fcpm082010 Electrical Specifications - Carel FCP/1 User Manual

Regulator with microprocessor control
Hide thumbs Also See for FCP/1:
Table of Contents

Advertisement

10.

Specifications and connections

10.1

FCPM082010 electrical specifications

Power supply
Analogue outputs
Digital outputs
Analogue inputs
Digital inputs
Serial outputs
Signal lights
Controller settings
Terminals and connectors
Operating conditions
Storage conditions
Index of protection
Environmental pollution
Protection against electric shock
PTI of the insulating materials
Period of stress across the insulating parts
Type of action -disconnection
Category of resistance to heat and fire
Immunity against voltage surges
Ageing characteristics
No. of automatic operating cycles
Software class and structure
Case
Dimensions
Assembly
Certification
Note 1:
The FCSER00000 option is required
Code +030220391 – rel 1.1 07/11/06
230 Vac single-phase. -15% +10% 50/60 Hz
1 phase control 0-230 Vac single-phase, 8 A (min 500mA)
1 phase control function for expansion with auxiliary power devices, MCHRTF*
0-5 V 5 mA max;
1 configurable input for
- ratiometric pressure probes 0-5V
- std Carel NTC temp. probes (10kΩ @25°C) range of measurement: –50°C +90°C
- std Carel NTC temp. probes (50kΩ @25°C) range of measurement: 0°C +120°C
- 0/10V control (Rin: 20 kΩ)
1 configurable input for
- ratiometric pressure probes 0-5V
- std Carel NTC temp. probes (10kΩ @25°C) range of measurement: –50°C +90°C
- std Carel NTC temp. probes (50kΩ @25°C) range of measurement: 0°C +120°C
1 configurable input for
- std Carel NTC temp. probes (10kΩ @25°C) range of measurement: –50°C +90°C
- std Carel NTC temp. probes (50kΩ @25°C) range of measurement: 0°C +120°C
measurement precision (excluding the probes):
- ratiometric probes: 1%
- 0/10V control: 5% (typical 2%)
- NTC probes 10kΩ: ±1°C [-10/50]; ±2°C [-40/-10 and 50/90]
- NTC probes 50kΩ: ±1°C [30/90]; ±2°C [0/30 and 90/120]
1 input with voltage free contact
typical voltage 12 V with contact open, typical current 6 mA with contact closed.
1 standard RS485 two wire connector [NOTE 1]
Carel supervisor and ModBus protocol; baud rate 19200; max length 1 km with shielded cable
Green power LED
Red alarm LED
Yellow serial connection active LED (flashes when receiving valid frame)
4 trimmers for manually setting:
- set point
- differential
- minimum speed
- maximum speed
4 dipswitches:
- select manual setting or configuration by parameters
- select function associated with the digital input
- enable double circuit (probe B2)
- enable Cut-off (or other settable function)
2 jumpers:
- 0/10V input configuration
Power supply and analogue outputs:
Screw terminals for cable cross-section min. 2.5 mm
Signals:
Spring terminals for cable cross-section max 2.5mm
4 pin JST connector for programming key
2
max 4 mm
2
.
2
.
-20/+50°C, <90% rH non-condensing
-20/+70°C, <90% rH non-condensing
IP54
2
Class I
250V
Long
1Y
Category D (UL94 – V0)
Category II
60,000 operating hours
100,000
Class A
Metallic (Al) with plastic cover (ball pressure test 75°C)
140x135x90 mm
Metal case fastened to panel or wall mounted using 4 screws dia. 3.5/4 mm
EMC:
EN 61326-1, EN 55014-1, EN 55014-2
Safety:
EN 60730-1
36
FCP manual
Table 10.a