To Connect the DPU to Test for Device Communication:
• Insert the programming plug in one end of Cable P/N 555-133891 into the red and black
jacks in the cable compartment in the bottom of the DPU.
• Attach the two alligator clip adaptors provided to the programming plug on
of cable P/N 555-133891. Connect one clip to the wire of Line 1 from the device loop to
be tested. Connect the other clip to the wire of Line 2 from the device loop to be tested.
To Connect the DPU to Test for Ground Faults:
• Make the connections described above to test for device communication.
• Insert the stacking banana plug of Cable P/N 555-133920 into the green jack in the
cable compartment in the bottom of the DPU.
• Connect the alligator clip on the other end of Cable P/N 555-133920 to Earth Ground.
Figure 3
Connecting The DPU To Test For Communication And Ground Faults
28
TESTING
With the DPU displaying the Main Menu, press the
LOOP TEST button. Note that this is visible only if the
DPU is set to the FireFinder-XLS / FS-250 / FC20
(FC2025, FC2050, FC2005, FC922, FC924 or FC901)
system. The DPU will show a display similar to the
following:
GROUND FAULT = NO
INTEL. DEVICES = 121
<SUMMARY
<EXIT
|
BOTTOM
DETAIL>
CHAPTER 3
CABLE P/N 555-133920
(5 ft. cable)
TO EARTH
GROUND
STACKING
BANANA
PLUG
GREEN
BANANA
JACK
OF DPU
the other
end