Siemens DPU User Manual page 16

Device programming unit
Table of Contents

Advertisement

DEVICE PROGRAMMING UNIT USER'S MANUAL
12
PROGRAMMING
FireFinder-XLS, FS-250, FC2025, FC2050, FC922 and
FC924 are limited to 252; for FC2005 and FC901
they are limited to 50.
The loop number will only appear if the DPU has been
configured for label printing.
Press ADDRESS. The cursor will appear under the
address number, allowing the user the option to
change the address setting by using the numerical
keypad.
Press PROGRAM. The DPU will prompt the user to
insert or connect a device. Once the device is
connected, the DPU will program the address. If the
detector or device is programmed successfully, the
label printer will print the number of labels selected
at setup and and the DPU will display the message
PROGRAMMED OK.
HFPT-11
LOOP=012 ADDRESS=111
PROGRAMMED OK
<EXIT
Press EXIT to return to the Main Menu. To change
the current setting of the detector or device, press
CHANGE to return to the loop and address setting
screen. Removing or disconnecting the device will
automatically increment the address and return to
the programming display.
If the data is entered out of range, the following
screen will flash for 3 seconds:
INCORRECT ENTRY!!!
If the unit could not be programmed correctly, the
display will show the message PROGRAMMING
FAILED and display a screen similar to the following:
Loop=1
ADDRESS=111
PROGRAMMING FAILED
<EXIT
|
CHANGE>
RE-DO>