Download Print this page

Immergas EOLO Star Instruction Booklet And Warning page 137

Hide thumbs Also See for EOLO Star:

Advertisement

Ignition block. The boiler lights up with each demand for room
heating or hot water production. If this does not occur within 10
seconds, the boiler goes on "ignition block" (indicator lamp 3 on). To
eliminate the block, turn the main switch (4) temporarily to the Reset
position. On first ignition or following a prolonged downtime the
ignition block may have to be inhibited. If this phenomenon occurs
frequently, contact a qualified technician for assistance (e.g. Immer-
gas Technical Service Centre).
Overtemperature block. During normal operation, if a fault causes
excessive internal overheating, the boiler goes on overtemperature
block (indicator lamp 3 flashing). After appropriate cooling, eliminate
the "overtemperature block" by turning the main switch (4) to Reset.
If this phenomenon occurs frequently, contact a qualified technician
for assistance (e.g. Immergas Technical Services Centre).
Air pressure switch failure. This occurs if the intake or exhaust
pipes are blocked or if a fan is blocked. If normal conditions are
restored the boiler restarts without having to be reset. If this anomaly
persists, contact a qualified technician for assistance (e.g. Immergas
Technical Assistance Service).
System delivery NTC sensor fault. If the unit detects an anomaly in
the system delivery NTC sensor, the boiler will not start; call a
qualified technician (e.g. the Immergas Technical Assistance Service).
Domestic circuit NTC sensor fault. If the unit detects an anomaly
in the domestic circuit NTC sensor, the boiler will not produce
domestic hot water; call a qualified technician (e.g. the Immergas
Technical Assistance Service).
Insufficient water circulating. This occurs if there is overheating in
the boiler due to insufficient water circulating in the primary circuit;
the causes can be:
- low circulation; check that no shutoff devices are closed on the
heating circuit and that the system is free of air (deaerated);
- circulating pump blocked; free the circulating pump.
If this phenomenon occurs frequently, contact a qualified technician
for assistance (e.g. Immergas Technical Services Centre).
Lack of water in boiler. Not enough water pressure detected in the
heating circuit to guarantee correct boiler operation. Make sure the
pressure in the system is between 1÷1.2 bar.
Domestic circuit leaks. If during operation in the heating phase
there is a temperature rise in domestic hot water the boiler signals
the anomaly and reduces the heating temperature to limit the
formation of scale in the exchanger.
Make sure that all the cocks of the domestic circuit are closed and
hot dripping, and in any case that there are no leaks in the circuit.
The boiler returns to normal functioning when optimal conditions are
restored in the domestic circuit.
If this anomaly persists, contact a qualified technician for assistance
(e.g. Immergas Technical Assistance Service).
Restoring heating system pressure.
Periodically check the system water pressure. The boiler pressure gauge
should read a pressure between 1 and 1.2 bar.
If the pressure falls below 1 bar (with the circuit cool) restore normal pressure
via the valve located at the bottom of the boiler (see figure).
N.B.: close the valve on completion.
If pressure values reach around 3 bar the safety valve may be activated.
In this case contact a professional technician for assistance.
In the event of frequent pressure drops, contact qualified personnel for
assistance to eliminate system leakage.
bottom view
gas cock
domestic water
inlet cock
Draining the system.
To drain the boiler, use the special drain cock.
Before draining, ensure that the filling valve is closed.
Anti-freeze protection.
The boiler is comes standard with an anti-freeze function that turns on the
pump and burner when system water temperature in the boiler falls below
4°C and stops once temperatures exceed 42°C The anti-freeze function is
guaranteed if the boiler is fully operative and not in "block" status, and is
electrically fed with the main switch is set to Summer or Winter. To avoid
continued operation in the event of prolonged absence, the system must
be drained completely or anti-freeze substances should be added to the
heating system water. In both cases the domestic water circuit of the boiler
must be drained. In appliances subject to frequent draining, the system
must be refilled with suitably treated water to eliminate hardness that may
cause the formation of scale.
drain cock
filler cock
ES
PT
GR
PL
TR
CZ
HR
SL
HU
RU
RO
GB
135

Advertisement

loading