3. Reverse any two of the unit power leads.
4. Reenergize to the compressor. Check pressures.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit will make an elevated level of noise and will
not provide cooling.
X. COOLING
Set space thermostat to OFF position. To start unit, turn on
main power supply. Set system selector switch at COOL
position and fan switch at AUTO. position. Adjust thermo-
stat to a setting below room temperature. Compressor starts
on closure of contactor.
Check unit charge. Refer to Refrigerant Charge section on
page 38.
Reset thermostat at a position above room temperature.
Compressor will shut off. Evaporator fan will shut off after a
30-second delay.
A. To Shut Off Unit
Set system selector switch at OFF position. Resetting ther-
mostat at a position above room temperature shuts unit off
temporarily until space temperature exceeds thermostat
setting. Units are equipped with Cycle-LOC™ protection
device. Unit shuts down on any safety trip, and indicator
light on thermostat comes on. Check reason for all safety
trips.
Compressor restart is accomplished by manual reset at the
thermostat by turning the selector switch to OFF and then to
ON position.
XI. MAIN BURNERS
Main burners are factory set and should require no
adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and ver-
ify that the burners light and evaporator fan is energized.
Check heating effect, then lower the thermostat setting
below the room temperature and verify that the burners and
evaporator fan turn off.
Refer to Tables 29A and 29B for the correct orifice to use at
high altitudes.
Table 29A — Altitude Compensation* —
581B036-072 Standard Units
72,000 AND 115,000 BTUH
NOMINAL INPUT
ELEVATION
Natural
(Ft)
Gas
Orifice
Size†
0-2,000
33
2,000
36
3,000
36
4,000
37
5,000
38
6,000
40
7,000
41
8,000
42
9,000
43
10,000
44
11,000
45
12,000
46
13,000
47
14,000
48
*As the height above sea level increases, there is less oxygen per cubic foot of
air. Therefore, heat input rate should be reduced at higher altitudes.
†Orifice available through your local Bryant distributor.
150,000 BTUH
NOMINAL INPUT
Liquid
Natural
Liquid
Propane
Gas
Propane
Orifice
Orifice
Orifice
Size†
Size†
Size†
43
30
38
44
31
39
45
31
40
45
32
41
46
32
42
47
34
43
48
35
43
49
36
44
50
37
45
50
39
46
51
41
47
52
42
48
52
43
49
53
44
50
Table 29B — Altitude Compensation* —
581B036-072 Low NOx Units
60,000 AND 90,000 BTUH
ELEVATION
Natural
(Ft)
Gas
Orifice
Size†
0-2,000
38
2,000
40
3,000
41
4,000
42
5,000
43
6,000
43
7,000
44
8,000
45
9,000
46
10,000
47
11,000
48
12,000
49
13,000
50
14,000
51
*As the height above sea level increases, there is less oxygen per cubic foot of
air. Therefore, heat input rate should be reduced at higher altitudes.
†Orifice available through your local Bryant distributor.
XII. HEATING
1. Purge gas supply line of air by opening union ahead
of the gas valve. If gas odor is detected, tighten union
and wait 5 minutes before proceeding.
2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating temper-
ature lever above room temperature.
4. The induced-draft motor will start.
5. After a call for heating, the main burners should light
within 5 seconds. If the burner does not light, then there
is a 22-second delay before another 5-second try. If the
burner still does not light, the time delay is repeated. If
the burner does not light within 15 minutes, there is a
lockout. To reset the control, break the 24-v power to W1.
6. The evaporator-fan motor will turn on 45 seconds
after burner ignition.
7. The evaporator-fan motor will turn off in 45 seconds
after the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within
the range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan motor on/off
delay is 45 seconds. The Integrated Gas Unit Controller (IGC)
modifies this value when abnormal limit switch cycles occur.
Based upon unit operating conditions, the on delay can be
reduced to 0 seconds and the off delay can be extended to 180
seconds. When one flash of the LED (light-emitting diode) is
observed, the evaporator-fan on/off delay has been modified.
If the limit switch trips at the start of the heating cycle dur-
ing the evaporator on delay, the time period of the on delay
for the next cycle will be 5 seconds less than the time at
which the switch tripped. (Example: If the limit switch trips
at 30 seconds, the evaporator-fan on delay for the next cycle
will occur at 25 seconds.) To prevent short-cycling, a 5-second
reduction will only occur if a minimum of 10 minutes has
elapsed since the last call for heating.
The evaporator-fan off delay can also be modified. Once the
call for heating has ended, there is a 10-minute period dur-
ing which the modification can occur. If the limit switch trips
during this period, the evaporator-fan off delay will increase
by 15 seconds. A maximum of 9 trips can occur, extending
the evaporator-fan off delay to 180 seconds.
To restore the original default value, reset the power to the
unit.
35
120,000 BTUH
NOMINAL INPUT
NOMINAL INPUT
Liquid
Natural
Propane
Gas
Orifice
Orifice
Size†
Size†
45
32
47
33
48
35
49
36
49
37
50
38
50
39
51
41
52
42
52
43
53
44
53
44
54
46
54
47
Liquid
Propane
Orifice
Size†
42
43
43
44
45
45
46
47
48
49
50
51
52
52