Bryant DURAPAC PLUS 581B Installation & Service Instructions Manual page 33

Single package rooftop gas heating/electric cooling units
Hide thumbs Also See for DURAPAC PLUS 581B:
Table of Contents

Advertisement

Table 28 — Fan Performance 581B072 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
0.2
CFM
Rpm
Bhp
1800
913
0.64
1900
952
0.73
2000
992
0.84
2100
1032
0.95
2200
1073
1.07
2300
1114
1.21
2400
1155
1.36
2500
1196
1.51
2600
1238
1.69
2700
1280
1.87
2800
1322
2.07
2900
1364
2.28
3000
1406
2.50
AIRFLOW
1.2
CFM
Rpm
Bhp
1800
1322
1.56
1900
1351
1.68
2000
1380
1.82
2100
1411
1.97
2200
1441
2.13
2300
1473
2.30
2400
1505
2.48
2500
1537
2.68
2600
1571
2.88
2700
2800
2900
3000
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1686 rpm. All other rpms require field-
supplied drive.
EXTERNAL STATIC PRESSURE (in. wg)
0.4
Watts
Rpm
Bhp
Watts
569
1010
0.80
715
652
1046
0.91
805
744
1083
1.02
903
844
1120
1.14
1010
954
1158
1.27
1127
1074
1196
1.41
1254
1204
1234
1.57
1391
1345
1273
1.73
1538
1497
1312
1.91
1697
1660
1352
2.10
1867
1835
1392
2.31
2050
2023
1432
2.53
2245
2224
1472
2.76
2452
EXTERNAL STATIC PRESSURE (in. wg)
1.4
Watts
Rpm
Bhp
Watts
1382
1388
1.77
1568
1495
1416
1.90
1686
1617
1444
2.04
1814
1748
1473
2.20
1950
1890
1503
2.36
2097
2041
1533
2.54
2254
2203
1564
2.73
2422
2376
2560
GENERAL FAN PERFORMANCE NOTES
1. Values include losses for filters, unit casing, and wet coils. See Fig. 38 and
Table 9 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full range
of the motor can be utilized with confidence. Using the fan motors up to
the ratings shown will not result in nuisance tripping or premature motor failure.
Unit warranty will not be affected. See Tables 7 and 8 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant repre-
sentative to verify.
4. Interpolation is permissible. Do not extrapolate.
0.6
Rpm
Bhp
Watts
Rpm
1098
0.98
869
1178
1131
1.09
965
1210
1166
1.21
1070
1242
1200
1.33
1184
1275
1236
1.47
1307
1308
1272
1.62
1440
1343
1308
1.78
1584
1377
1345
1.96
1738
1412
1382
2.14
1904
1448
1420
2.34
2081
1484
1458
2.56
2270
1521
1496
2.78
2472
1.6
Rpm
Bhp
Watts
Rpm
1451
1.98
1762
1510
1477
2.12
1885
1536
1505
2.27
2017
1563
1533
2.43
2159
1590
1562
2.60
2311
1618
1591
2.79
2474
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See below for general fan performance notes.
33
0.8
1.0
Bhp
Watts
Rpm
Bhp
1.16
1032
1252
1.35
1.28
1134
1282
1.48
1.40
1245
1313
1.61
1.54
1365
1345
1.75
1.68
1495
1377
1.90
1.84
1634
1409
2.07
2.01
1784
1443
2.24
2.19
1945
1477
2.43
2.38
2117
1511
2.63
2.59
2300
1546
2.84
2.81
2496
1.8
2.0
Bhp
Watts
Rpm
Bhp
2.21
1962
1568
2.44
2.35
2090
1593
2.59
2.51
2227
1619
2.75
2.67
2374
2.85
2532
Watts
1203
1311
1427
1553
1689
1834
1990
2157
2335
2526
Watts
2169
2302
2443