Bryant DURAPAC PLUS 581B Installation & Service Instructions Manual page 16

Single package rooftop gas heating/electric cooling units
Hide thumbs Also See for DURAPAC PLUS 581B:
Table of Contents

Advertisement

IMPORTANT: If the power exhaust accessory is to be
installed on the unit, the hood shipped with the unit will not
be used and must be discarded. Save the aluminum filter
for use in the power exhaust hood assembly.
3. The indoor coil access panel will be used as the top of
the hood. Remove the screws along the sides and bot-
tom of the indoor coil access panel. See Fig. 24.
4. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
screws provided to attach the hood sides to the unit.
See Fig. 25.
5. Remove the shipping tape holding the economizer
barometric relief damper in place.
6. Insert the hood divider between the hood sides. See
Fig. 25 and 26. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
INDOOR
COIL
ACCESS
PANEL
Fig. 24 — Indoor Coil Access Panel Relocation
LEFT
HOOD
SIDE
B
19 1/16"
HOOD DIVIDER
Fig. 25 — Outdoor-Air Hood Construction
SIDE
PANEL
TOP
SIDE
PANEL
CAULK
HERE
INDOOR
COIL
ACCESS
PANEL
TOP
PANEL
INDOOR COIL
ACCESS PANEL
SCREW
33 3/8"
DIVIDER
BAROMETRIC
RELIEF
Fig. 26 — Filter Installation
7. Open the filter clips which are located underneath
the hood top. Insert the aluminum filter into the bot-
tom filter rack (hood divider). Push the filter into
position past the open filter clips. Close the filter clips
to lock the filter into place. See Fig. 26.
8. Caulk the ends of the joint between the unit top panel
and the hood top. See Fig. 24.
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV
wiring is shown in Fig. 27.
Barometric flow capacity is shown in Fig. 28. Outdoor air
leakage is shown in Fig. 29. Return air pressure drop is
shown in Fig. 30.
F. EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoor-air temperature.
The outdoor-air temperature is used to determine when the
EconoMi$er IV can be used for free cooling. The sensor is
factory-installed on the EconoMi$er IV in the outdoor
airstream. See Fig. 21. The operating range of temperature
measurement is 40 to 100 F.
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. See Fig. 31. This sensor
is factory installed. The operating range of temperature
measurement is 0° to 158 F. See Table 3 for sensor tempera-
ture/resistance values.
The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the "crimp end"
and is sealed from moisture.
Outdoor Air Lockout Sensor
The EconoMi$er IV is equipped with an ambient tempera-
ture lockout switch located in the outdoor airstream which is
used to lockout the compressors below a 42 F ambient tem-
perature. See Fig. 21.
16
17 1/4"
OUTSIDE
AIR
HOOD
CLEANABLE
ALUMINUM
FILTER
FILTER
FILTER
CLIP

Advertisement

Table of Contents
loading

Table of Contents

Save Article as PDF