Bryant DURAPAC PLUS 551B Installation, Start-Up And Service Instructions Manual

Durapac plus series single package rooftop electric cooling units

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-37
I. Step 1 - Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 - Field Fabricate Ductwork . . . . . . . . . . . . . 1
and External Trap. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
IV. Step 4 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . 2
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38-41
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41-45
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .46-49
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguisher available for all brazing operations.
CAUTION: Ensure voltage listed on unit data plate
agrees with electrical supply provided for unit.
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch
to unit and install lockout tag. Electrical shock could
cause personal injury.

INSTALLATION

Unit is shipped in the vertical configuration. To convert to
horizontal configuration, remove side duct opening covers.
Using the same screws, install covers on vertical duct open-
ings with the insulation-side down. Seals around duct
openings must be tight. See Fig. 1.
installation, start-up and
service instructions
SINGLE PACKAGE ROOFTOP
ELECTRIC COOLING UNITS
Page
Dura Pac Plus Series
Cancels: II 551B-90-6
I. STEP 1 - PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. Install insulation, cant
strips, roofing felt, and counter flashing as shown. Ductwork
must be attached to curb. If electric or control power is to be
routed through the basepan, attach the accessory thru-the-
bottom service connections to the basepan in accordance
with the accessory installation instructions. Connections
must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the
roof curb as shown in Fig. 2. Improperly applied gasket can
also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to func-
tion properly. Unit leveling tolerances are shown in Fig. 3.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required.
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a gravel apron in front of con-
denser coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
C. Alternate Unit Support (Curb or Slab Mount)
A non-combustible sleeper rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the
long sides of the unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
II. STEP 2 - FIELD FABRICATE DUCTWORK
On vertical discharge units, secure all ducts to roof curb and
building structure. Do not connect ductwork to unit. For hori-
zontal applications, field-supplied flanges should be attached
to horizontal discharge openings and all ductwork attached
to the flanges. Insulate and weatherproof all external duct-
work, joints, and roof openings with counter flashing and
mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insu-
lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with appli-
cable fire codes.
A minimum clearance to combustibles is not required around
ductwork on vertical discharge units. On horizontal dis-
charge units, a minimum clearance of 1 in. is required for the
first 12 in. of ductwork. Cabinet return-air static pressure (a
negative condition) should not exceed 0.30 in. wg with
EconoMi$er IV, or 0.45 in. wg without economizer.
551B
Sizes 090-150
7
/
to 12
/
Tons
1
1
2
2
II 551B-90-7
10/15/05

Advertisement

Table of Contents
loading

Summary of Contents for Bryant DURAPAC PLUS 551B

  • Page 1: Table Of Contents

    installation, start-up and service instructions SINGLE PACKAGE ROOFTOP ELECTRIC COOLING UNITS CONTENTS SAFETY CONSIDERATIONS ......1 INSTALLATION .
  • Page 2: Step 3 - Install Condensate Drain Line And External Trap

    III. STEP 3 — INSTALL CONDENSATE DRAIN LINE AND EXTERNAL TRAP Condensate drain connections are located at the bottom and end of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used in vertical or horizontal applications.
  • Page 3 CONNECTOR D ALT PKG. ACCY. DRAIN HOLE CRBTMPWR001A01 CRBTMPWR002A01 ″ ″ 2′-8 1′-10 CRBTMPWR003A01 [827] [583] [44.5] CRBTMPWR004A01 ACCESSORY POWER CONTROL ″ [19] NPT ″ ″ [31.7] [19] NPT ″ ″ ″ ″ [19] NPT [12.7] NPT [12.7] NPT [12.7] NPT ″...
  • Page 4 MAXIMUM ALLOWABLE DIFFERENCE (in.) Fig. 3 — Unit Leveling Tolerances HORIZONTAL DRAIN PLUG DRAIN OUTLET NOTE: Drain plug is shown in factory-installed position. Fig. 4 — Condensate Drain Location NOTES: 1. Place unit on curb as close as possible to the duct end. 2.
  • Page 5 — —...
  • Page 6 UNIT 551B NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit EconoMi$er IV Perfect Humidity™ Dehumidification Package Roof Curb COMPRESSOR Quantity Oil (oz) (each compressor) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Standard Unit Circuit 1 Circuit 2 Unit With Perfect Humidity Dehumidification Package Circuit 1 Circuit 2 CONDENSER FAN...
  • Page 7: Step 5 - Make Electrical Connections

    Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty. See Table 3 for electric heater and single point box usage. Laboratories) COMP(S) —...
  • Page 8 VOLTAGE RANGE UNIT NOMINAL CONV 551B V-PH-Hz TYPE OUTLET 208/230-3-60 HIGH STATIC HIGH STATIC 460-3-60 HIGH STATIC HIGH STATIC 575-3-60 HIGH STATIC HIGH STATIC 208/230-3-60 HIGH STATIC HIGH STATIC 460-3-60 HIGH STATIC HIGH STATIC See page 10 for legend and notes. Table 2 —...
  • Page 9 VOLTAGE RANGE UNIT NOMINAL CONV 551B V-PH-Hz TYPE OUTLET 575-3-60 (cont) HIGH STATIC HIGH STATIC 208/230-3-60 HIGH STATIC HIGH STATIC 460-3-60 HIGH STATIC HIGH STATIC 575-3-60 HIGH STATIC HIGH STATIC 208/230-3-60 460-3-60 575-3-60 See page 10 for legend and notes. Table 2 —...
  • Page 10 LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP— Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA —...
  • Page 11: Step 6 - Adjust Factory-Installed Options

    This is available through the local Bryant distributor. This kit is required to ensure a reliable water-tight connection. 2. If unit is mounted on roof curb and accessory thru- the-bottom service connections are used, route wire through connections.
  • Page 12 Perfect Humidity solenoid valve and must be wired between the Perfect Humidity fuse and the low- pressure switch. Refer to the installation instructions included with the Bryant Light Commercial Thermi- distat device for more information. ROOF TOP UNIT 3.2 AMPS...
  • Page 13 C. Convenience Outlet An optional convenience outlet provides power for rooftop use. For maintenance personnel safety, the convenience out- let power is off when the unit disconnect is off. Adjacent unit outlets may be used for service tools. An optional “Hot Out- let”...
  • Page 14 2. The box with the economizer hood components is shipped in the compartment behind the economizer. The EconoMi$er IV controller is mounted on top of the EconoMi$er IV in the position shown in Fig. 19. To remove the component box from its shipping posi- tion, remove the screw holding the hood box bracket to the top of the economizer.
  • Page 15 LEFT HOOD SCREW SIDE 24 9/16” HOOD DIVIDER Fig. 23 — Outdoor-Air Hood Construction LEGEND Potentiometer Defaults Settings: Power Exhaust DCV— Demand Controlled Ventilation Minimum Pos. IAQ — Indoor Air Quality DCV Max. LA — Low Ambient Lockout Device DCV Set OAT —...
  • Page 16 2500 2000 1500 1000 0.15 0.05 STATIC PRESSURE (in. wg) Fig. 26 — Barometric Relief Flow Capacity 0.13 0.20 0.22 0.25 0.30 0.35 0.40 STATIC PRESSURE (in. wg) Fig. 27 — Outdoor Air Damper Leakage 6000 5000 4000 3000 2000 1000 0.05 0.10...
  • Page 17 Outdoor Dry Bulb Changeover The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable set point selected on the control.
  • Page 18 Indoor Air Quality (IAQ) Sensor Input The IAQ input can be used for demand control ventilation control based on the level of CO measured in the space or return air duct. Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and CONTROL CONTROL POINT CURVE...
  • Page 19 Exhaust Set Point Adjustment The exhaust set point will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. See Fig. 30. The set point represents the damper position above which the exhaust fans will be turned on.
  • Page 20 See Table 7. Use setting 1 or 2 for Bryant equipment. See Table 7. 1. Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.
  • Page 21: Step 7 - Adjust Evaporator-Fan Speed

    VII. STEP 7 — ADJUST EVAPORATOR-FAN SPEED Adjust evaporator-fan rpm to meet jobsite conditions. For units with electric heat, required minimum cfm is 2250 for 551B090 and 102 and 3000 for 551B120 and 150. See Table 8 for exceptions. Table 8 — Minimum Required Airflow Exceptions UNIT UNIT HEATER...
  • Page 22 Fig. 38 — Typical Belt-Drive Motor Mounting for Sizes 102-150 Table 9 — Fan Rpm at Motor Pulley Setting*; Standard Motor/Drive UNIT 551B 090,102 1085 1060 1035 1080 1060 1035 1130 1112 1087 *Approximate fan rpm shown. Table 10 — Fan Rpm at Motor Pulley Setting*; High-Static Motor/Drive UNIT 551B 1080...
  • Page 23 2. Values include losses for filters, unit casing, and wet coils. See Tables 13 and 14 and Fig. 36 for accessory/FIOP static pressure information. 3. Use of a field-supplied motor may affect wire sizing. Contact Bryant representative to verify. 4. Interpolation is permissible. Do not extrapolate. — —...
  • Page 24 Table 15 — Fan Performance 551B090 — Vertical Discharge Units; Standard Motor (Belt Drive)* AIRFLOW Watts 2250 0.53 2300 0.56 2400 0.61 2500 0.67 2550 0.71 2600 0.74 2700 0.81 2800 0.89 2900 0.97 3000 1.06 3100 1.15 1071 3200 1.25 1162 3300...
  • Page 25 Table 16 — Fan Performance 551B090 — Vertical Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW Watts 2250 0.53 2300 0.56 2400 0.61 2500 0.67 2550 0.71 2600 0.74 2700 0.81 2800 0.89 2900 0.97 3000 1.06 3100 1.15 1071 3200 1.25 1162 3300...
  • Page 26 Table 17 — Fan Performance 551B102 — Vertical Discharge Units; Standard Motor (Belt Drive)* AIRFLOW Watts 2500 0.41 2600 0.45 2700 0.50 2800 0.55 2900 0.59 3000 0.65 3100 0.70 3200 0.76 3300 0.83 3400 0.89 3500 0.96 3600 1.04 3700 1.11 1040...
  • Page 27 Table 18 — Fan Performance 551B102 — Vertical Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW Watts 2500 0.41 2600 0.45 2700 0.50 2800 0.55 2900 0.59 3000 0.65 3100 0.70 3200 0.76 3300 0.83 3400 0.89 3500 0.96 3600 1.04 3700 1.11 1040...
  • Page 28 Table 19 — Fan Performance 551B120 — Vertical Discharge Units; Standard Motor (Belt Drive* AIRFLOW Watts 3000 0.65 3100 0.70 3200 0.76 3300 0.83 3400 0.89 3500 0.96 3600 1.04 3700 1.11 1040 3800 1.20 1116 3900 1.28 1197 4000 1.37 1281 4100...
  • Page 29 Table 20 — Fan Performance 551B120 — Vertical Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW Watts 3000 0.65 3100 0.70 3200 0.76 3300 0.83 3400 0.89 3500 0.96 3600 1.04 3700 1.11 1040 3800 1.20 1116 3900 1.28 1197 4000 1.37 1281 4100...
  • Page 30 Table 21 — Fan Performance 551B150 — Vertical Discharge Units; Standard Motor (Belt Drive)* AIRFLOW Watts 3700 1.11 1040 3800 1.20 1116 3900 1.28 1197 4000 1.37 1281 4100 1.47 1370 4200 1.57 1462 4300 1.67 1559 4400 1.78 1660 4500 1.89 1766...
  • Page 31 Table 22 — Fan Performance 551B090 — Horizontal Discharge Units; Standard Motor (Belt Drive)* AIRFLOW Watts 2250 0.43 2300 0.45 2400 0.49 2500 0.54 2550 0.56 2600 0.59 2700 0.64 2800 0.70 2900 0.75 3000 0.82 3100 0.88 3200 0.95 3300 1.03 3400...
  • Page 32 Table 23 — Fan Performance 551B090 — Horizontal Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW Watts 2250 0.43 2300 0.45 2400 0.49 2500 0.54 2550 0.56 2600 0.59 2700 0.64 2800 0.70 2900 0.75 3000 0.82 3100 0.88 3200 0.95 3300 1.03 3400...
  • Page 33 Table 24 — Fan Performance 551B102 — Horizontal Discharge Units; Standard Motor (Belt Drive)* AIRFLOW Watts 2500 0.37 2600 0.41 2700 0.45 2800 0.49 2900 0.53 3000 0.58 3100 0.63 3200 0.68 3300 0.74 3400 0.80 3500 0.86 3600 0.93 3700 1.00 3800...
  • Page 34 Table 25 — Fan Performance 551B102 — Horizontal Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW Watts 2500 0.37 2600 0.41 2700 0.45 2800 0.49 2900 0.53 3000 0.58 3100 0.63 3200 0.68 3300 0.74 3400 0.80 3500 0.86 3600 0.93 3700 1.00 3800...
  • Page 35 Table 26 — Fan Performance 551B120 — Horizontal Discharge Units; Standard Motor (Belt Drive)* AIRFLOW Watts 3000 0.58 3100 0.63 3200 0.68 3300 0.74 3400 0.80 3500 0.86 3600 0.93 3700 1.00 3800 1.07 3900 1.15 1069 4000 1.23 1144 4100 1.31 1223...
  • Page 36 Table 27 — Fan Performance 551B120 — Horizontal Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW Watts 3000 0.58 3100 0.63 3200 0.68 3300 0.74 3400 0.80 3500 0.86 3600 0.93 3700 1.00 3800 1.07 3900 1.15 1069 4000 1.23 1144 4100 1.31 1223...
  • Page 37 Table 28 — Fan Performance 551B150 — Horizontal Discharge Units; Standard Motor (Belt Drive)* AIRFLOW Watts 3700 1.00 3800 1.07 3900 1.15 1069 4000 1.23 1144 4100 1.31 1223 4200 1.40 1305 4300 1.49 1392 4400 1.59 1482 4500 1.69 1577 4600 1.80...
  • Page 38: Pre-Start-Up

    PRE-START-UP WARNING: Failure to observe the following warn- ings could result in serious personal injury: 1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any elec- tric power to unit unless compressor terminal cover is in place and secured.
  • Page 39 IX. COOLING To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO position. Adjust thermostat to a setting below room temperature. Compressor starts on closure of contactor. Check unit charge. Refer to Refrigerant Charge section on page 42.
  • Page 40 Fig. 40 — Perfect Humidity™ System Normal Design Cooling Operation Subcooling Mode When subcooling mode is initiated, this will energize (close) the liquid line solenoid valve (LLSV) forcing the hot liquid refrigerant to enter into the subcooling coil (see Fig. 41). As the hot liquid refrigerant passes through the subcooling/ reheat dehumidification coil, it is exposed to the cold supply airflow coming through the evaporator coil.
  • Page 41: Service

    Table 29 — Perfect Humidity™ Dehumidification System Sequence of Operation THERMOSTAT ECONOMIZER FUNCTION INPUT OAT < Economizer Set Point — — LEGEND — Outdoor Air Temperature NOTE: On a thermostat call for W1, all cooling and dehumidification will be off. F.
  • Page 42 Refer to Optional EconoMi$er IV section on page 13. VI. REFRIGERANT CHARGE Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Refer to Bryant Standard Service Techniques Manual, Chapter 1, Refrigerants section. Unit panels must be in place when unit is operating during charging procedure.
  • Page 43 Fig. 47 — Cooling Charging Charts, Standard 551B090 Unit Fig. 48 — Cooling Charging Charts, Standard 551B102 Unit — —...
  • Page 44 Fig. 49 — Cooling Charging Charts, Standard 551B120 Unit Fig. 50 — Cooling Charging Charts, Standard 551B150 Unit — —...
  • Page 45 VII. REPLACEMENT PARTS A complete list of replacement parts may be obtained from any Bryant distributor upon request. NOTE: When using the charging charts, it is important that only the subcooling/ reheat dehumidification coil liquid line solenoid valve be energized. The subcool-...
  • Page 46: Troubleshooting

    TROUBLESHOOTING I. UNIT TROUBLESHOOTING Refer to Tables 30-32 for additional information. PROBLEM Compressor(s) and Power failure. Condenser Fan Fuse blown or circuit breaker tripped. Will Not Start. Defective thermostat, contactor, transformer, control relay. Insufficient line voltage. Incorrect or faulty wiring. Thermostat setting too high.
  • Page 47 Table 31 — Perfect Humidity™ Dehumidification System Subcooling Mode Service Analysis PROBLEM Subcooling Mode (Liquid Reheat) No power to control transformer from Will Not Energize. evaporator-fan motor. No power from control transformer to liquid line solenoid valve. Liquid line solenoid valve will not operate. Liquid line solenoid valve will not open.
  • Page 48 A functional view of the EconoMi$er IV is shown in Fig. 54. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is avail- able from Bryant to help with EconoMi$er IV training and troubleshooting. A. EconoMi$er IV Preparation This procedure is used to prepare the EconoMi$er IV for troubleshooting.
  • Page 49 4. Remove the jumper across T and T1. The actuator should drive fully closed. 5. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. G. EconoMi$er IV Troubleshooting Completion This procedure is used to return the EconoMi$er IV to opera- tion.
  • Page 50: Index

    Perfect Humidity™ dehumidification package 39-41 Outdoor air hood 13-15 Outdoor air temperature sensor Outdoor air inlet screens Cleaning Copyright 2005 Bryant Heating & Cooling Systems INDEX Perfect Humidity™ dehumidification system 11, 12, 21, 39-42, 45, 47 Physical data Power supply Wiring...
  • Page 52: Start-Up Checklist

    REFRIGERANT DISCHARGE, CIRCUIT 2 VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGES 43-45. Copyright 2005 Bryant Heating & Cooling Systems START-UP CHECKLIST (Remove and Store in Job File) SERIAL NO.: ___________________________________________...

Table of Contents

Save Article as PDF