Bosch FPA-1000 Release Notes page 15

Analog addressable fire panels
Hide thumbs Also See for FPA-1000:

Advertisement

Analog Addressable Fire Panels
9.2
Issues Fixed in Version 1.02
9.3
Known Issues in Version 1.02
10
Release Notes for Version 1.01
10.1
New Features in Version 1.01
With Version 1.01, the panel's display supports Spanish and Portuguese.
10.2
Issues Fixed in Version 1.01
10.3
Known Issues in Version 1.01
Bosch Security Systems, Inc.
Increased reset time to allow conventional devices connected to the FLM-325-CZM4 a
longer time to power off. This fixes an issue where sometimes it was required to press
the Reset button a second time before the system would unlatch the alarm from a
conventional device.
Troubles and restorals are occasionally reported if a D7035 Octal Relay Module is
installed on the Option bus.
Level 3 PIN login is blocked on the Web page: Sometimes Level 3 PIN cannot login any
more. The user must reset the Level 3 PIN from the panel menu.
28-day Auto Test Interval: When setting the auto test interval to 28 days, the next auto
test report is sent approximately 1 hour later than expected.
Communication loss counters for Supervised Output Modules: If there are more than
100 FLM-325-N4 devices on an SLC, the loss counter values for the FLM-325-N4 devices
on the SLC diagnostics menu are not always zero.
Confirmation for remote programming access: As soon as the option Confirm At Panel is
enabled from the menu, web programming is allowed for 25 minutes. Remote
programming is disabled 25 minutes later.
FAA-325-B6S menu for the detector: The menu Edit Sounder Base for detectors is not
working. The menu was intended as a shortcut from Add A Device or Edit A Device to Edit
Sounder Base when programming SLC devices.
No missing trouble reported if SLC card is unplugged while power is applied to the panel.
On the Web page, the delay mode for the FLM-325-CZM4 is grayed out if the choice is not
allowed.
Troubles and restorals are occasionally reported if a D7035 Octal Relay Module is
installed on the Option bus.
Level 3 PIN login is blocked on the Web page: Sometimes Level 3 PIN cannot login any
more. The user must reset the Level 3 PIN from the panel menu.
28-day Auto Test Interval: When setting the auto test interval to 28 days, the next auto
test report is sent approximately 1 hour later than expected.
Communication loss counters for Supervised Output Modules: If there are more than
100 FLM-325-N4 devices on an SLC, the loss counter values for the FLM-325-N4 devices
on the SLC diagnostics menu are not always zero.
Confirmation for remote programming access: As soon as the option Confirm At Panel is
enabled from the menu, web programming is allowed for 25 minutes. Remote
programming is disabled 25 minutes later.
Release Notes
Release Notes for Version 1.01 | en
F.01U.075.638 | 08 | 2012.08