en | Release Notes for Version 1.12
4.2
Issues Fixed in Version 1.13
4.3
Known Issues in Version 1.13
5
Release Notes for Version 1.12
5.1
New Features in Version 1.12
No new features introduced in this version.
5.2
Issues Fixed in Version 1.12
F.01U.075.638 | 08 | 2012.08
Alarm Verification Issue: The issue where the version 1.10, 1.11 or 1.12 FPA-1000 FACP
may fail to recognize a verified smoke alarm when the Alarm Verification feature is turned
on has been corrected for analog SLC detectors.
Answer unknown trouble: When remote access is enabled, incoming calls (non-modem)
result in a trouble message. Currently, a "work around" is to disable remote access.
New SLC devices: The FAP-325-T Analog Multisensor Detector is in the literature as SLC
device, but is not available yet.
4-Wire Alarm Verification: The Alarm Verifiaction Delay type is not listed for 4-wire
detectors connected to a an FLM-325-CZM4 module or with contact modules (FLM-325-I/
-I4/-!4-A/-I4-AI/-2I4/-IM or D326A).
Display changes: Instead of group, the panel displays the highest priority event. If any
higher priority event comes in, the panel automatically switches to the new event.
Dual-zones improvement: Changed the layout of the dual zone mapping in the web
browser. Changed the name of "group" in Progrmming dual zones to "pairs." Set the
maximum co-dependent zones of one zone to four different zones.
Hexadecimal reporting account number: Regardless of which reporting format (menu/
web browser) is used, the panel can be programmed with hexadecimal reporting account
numbers.
Point restoral upon reset: Upon panel reset, the panel restores all existing alarms
including fire/waterflow alarms, gas alarms, and supervisory alarms. This involves
removing alarms from display and creating alarm restoral events of all existing alarms for
history, reporting, and printing.
Ring count programming: To delay the panel answering an incoming call on shared
phone line 1, you can program up to 10 rings after which the panel will answer.
Trouble beep at system initializing: Upon system initialization, the panel sounds the
buzzer in trouble mode and lights the trouble LED until the system is normal or until a
real trouble is indicated.
Auto dialing type: The auto dialing function has been fixed so that it correctly tests both
pulse and tone dialing.
Battery trouble: Fixed issue with battery restore being reported even without battery
connection.
IP reporting with encryption and anti-replay: Fixed the communication issue that occurs
in v1.10 and v1.11 if both IP reporting with encryption and anti-replay are turned on and
the reporting format is Modem IIIa
chosen, some events cannot be sent to the receiver. After several retries, a
communication fail event is shown on the panel.
2
with text. In these versions with this combination
Release Notes