Bosch FPA-1000 Release Notes page 13

Analog addressable fire panels
Hide thumbs Also See for FPA-1000:

Advertisement

Analog Addressable Fire Panels
8
Release Notes for Version 1.03
8.1
New Features in Version 1.03
No new features
8.2
Issues Fixed in Version 1.03
Bosch Security Systems, Inc.
Communication loss counters for Supervised Output Modules: If there are more than
100 FLM-325-N4 devices on an SLC, the loss counter values for the FLM-325-N4 devices
on the SLC diagnostics menu are not always zero.
Indication of remaining time during Walk Test on Web: Not available yet.
Forbidden characters for label text on Web page:
The following characters must not be used on Web pages: < > & " ' .
The following characters are not displayed correctly on the panel's LCD: % \ ~
New SLC devices: The following SLC devices are in the literature but not available yet:
FAP-325-T Analog Multisensor Detector Analog Multisensor Detector
FLM-325-I4-A Contact Monitor 4-inch Class A
FLM-325-I4-AI Contact Monitor 4-inch Class A w/Isolator
FLM-325-2R4-2A Dual Relay Module 2 A
FLM-325-2R4-2AI Dual Relay Module 2 A w/Isolator
FLM-325-2R4-8A Dual Relay Module 8 A
FLM-325-2R4-8AI Dual Relay Module 8 A w/Isolator
Installation and Operation Guide (IOG) Version 3.0:
Page 85: It says, " If the panel is already silenced, pressing [SILENCE] causes an
unsilence command in the panel". This feature was removed and the statement will
be removed from the IOG accordingly in the next revision.
Silenceable options: The silenceable options for the Mainboard and Option Bus
relays are not shown on the product MMI, but replaced by [EXT SIGNALING].
Page 133: The Web login screenshot on the page below shows a RESET button. Such
button is not available on the product Web page.
Page 136: The description about the item "Compare Configuration" does not exactly
match the software functionality. In fact, it should say, "You can compare either two
different FPA-1000-UL configuration? files or preview saved/unimplemented
changes".?
Real-time event printing features including programmable delay: This feature is
described in the IOG and Online Help, but is not yet available on MMI and Web page.
Compare Configuration: With the IE Web browser, the "Compare Configuration" page
cannot be saved as a file. (It works with the Mozilla Firefox browser.)
Web access: After having confirmed, the user needs to reconfirm the Web access on the
panel if no activities have been performed for 25 minutes. Sometimes after confirmation,
reconfirmation is required before the time out of 25 minutes.
Menu 3.2.4: When having selected from menu 3.2.4, sometimes the panel prints the SLC
diag pages multiple times until the user exits the menu.
Off hook time: When accessing the panel remotely through the phone line the off hook
time of a dropped call is reduced.
This fixes an issue that the panel didn't hang off in time after a remote call was dropped.
Powered IN terminals in Class B mode: This fixes an issue when the CZM which is wired
in Class B mode provided voltage to the IN terminals when there is an open trouble.
Release Notes
Release Notes for Version 1.03 | en
F.01U.075.638 | 08 | 2012.08
13