Download Print this page

Bosch FPA-1000 Release Notes page 14

Analog addressable fire panels
Hide thumbs Also See for FPA-1000:

Advertisement

14
en | Release Notes for Version 1.02
8.3
Known Issues in Version 1.03
9
Release Notes for Version 1.02
9.1
New Features in Version 1.02
No new features
F.01U.075.638 | 08 | 2012.08
Open trouble and power loss at IN terminals: This fixes an issue when a Class A or
Class B wired CZM which is connected to external auxiliary power has an open loop or
open EOL during the "Auto Learn Difference" operation or "Add A Device" operation from
the panel menu, there is no open trouble indication and there will be no power provided
to the IN terminals. The devices between the IN terminals and the break will not have
power.
Aux power trouble and Auto Learn: This fixes an issue that the CZM does not display the
Aux power trouble when Aux power is missing and "Auto Learn" or "Auto Learn
Difference" or "Add A device" from the panel menu was performed.
Power loss at IN terminals after reset: This fixes an issue when the CZM is wired in
Class A mode and connected to external auxiliary power, and a open trouble is shown at
the panel. The CZM provides voltage to both OUT and IN terminals. If there is still a break
in the loop and reset is pressed, the devices connected to the IN terminals would lose
power.
Open trouble and global reset: This fixes an issue when the CZM which is wired in
Class A mode and connected to AUX/RST power still reads and displays the CZM as being
in the open state even after repairing the Class A loop and pressing reset.
28-day Auto Test Interval: This fixes an issue where the next auto test report is sent
approximately 1 hour later than expected, when setting the auto test interval to 28 days.
FAA-325-B6S menu for the detector: The menu item Edit Sounder Base for detectors is
removed. The menu was intended as a shortcut from Add A Device or Edit A Device to Edit
Sounder Base when programming SLC devices.
The FPA-1000-UL Installation and Operation Guide will be updated accordingly with
Version 3.0.
Listing of SLC devices after "Auto Learn Difference": This fixes an issue when a new
device address is less than the greatest address of the existing devices, after "Auto Learn
Difference" operation the SLC loop devices were not displayed completely in Internet
Explorer.
CZM modules per SLC: The number of Conventional Zone Modules (FLM-325-CZM4) per
SLC module is limited to 32.
Level 3 PIN login is blocked on the Web page: Sometimes Level 3 PIN cannot login any
more. The user must reset the Level 3 PIN from the panel menu.
Communication loss counters for Supervised Output Modules: If there are more than
100 FLM-325-N4 devices on an SLC, the loss counter values for the FLM-325-N4 devices
on the SLC diagnostics menu are not always zero.
Confirmation for remote programming access: As soon as the option Confirm At Panel is
enabled from the menu, web programming is allowed for 25 minutes. Remote
programming is disabled 25 minutes later.
Release Notes
Analog Addressable Fire Panels
Bosch Security Systems, Inc.

Advertisement

loading