Bosch FPA-1000 Release Notes page 12

Analog addressable fire panels
Hide thumbs Also See for FPA-1000:

Advertisement

12
en | Release Notes for Version 1.10
7.2
Issues Fixed in Version 1.10
7.3
Known Issues in Version 1.10
F.01U.075.638 | 08 | 2012.08
NAC appliances (refer to FPA-1000-UL NAC Compatibility List, P/N F.01U.075.636):
New Wheelock and System Sensor devices have been added to the compatible
devices' list
Gentex devices registered
Mainboard/Option Bus NAC patterns include Gentex
Built-in synchronization for appliances from Gentex
NAC patterns for global gas alarm zone include Temporal Code 4.
Programming option for IP reporting communication with the Advanced Encryption
Standard (AES)
Programming option for SIA 300 and Modem IIIa
text
Programming option for silence operation for relays and City Ties
Programmable reset enable/disable option of the auxiliary power supply AUX/RST upon
panel reset
Programming options for sequential reset of Mainboard and Option Bus relays
Global delay alarm option
Programming option for sandwich alarm allows time-triggered phased evacuation
(evacuation floor above, floor below)
Dual-zone alarm allows for programming a dual-zone dependency
Auto logout indication at Level 3
Simplified software version indication (refer to Section 1.2 Version Naming of the
FPA-1000 Software)
Translation of the panel MMI and Web pages into the languages Portuguese and Spanish
New features on the Web pages:
Off-line configuration tool
Online help
Allows for comparing and printing the programmed configuration
Allows timezone offset for time synchronization with PC
Gas alarm: Gas alarms are reported to the central station receiver as event type Fire
Supervisory, if Modem IIIa
not sent to the central station receiver.
History records for manual/automatic communicator tests: Each communication test is
recorded in history. It was not recorded in previous versions.
Fire trouble/restoral event codes: If Modem IIIa
restoral event codes are transmitted, instead of general trouble/restoral event codes.
Confirmation for remote programming access: As soon as the option Confirm At Panel is
enabled from the menu, web programming is allowed for 25 minutes. Remote
programming is disabled 25 minutes later.
Phone line 1 disconnection: The panel would sometimes indicate that the phone line 1
was disconnected after being installed for some period of time, preventing the DACT
from transmitting reports via PSTN.
Level 3 PIN login is blocked on the Web page: Sometimes Level 3 PIN cannot login any
more. The user must reset the Level 3 PIN from the panel menu.
Panel reset: When resetting the panel, no fire restoral messages will be sent.
2
2
format is programmed. This fixes an issue that Gas alarm is
2
Release Notes
Analog Addressable Fire Panels
reporting formats: With text or without
format is programmed, Fire trouble/