Summary of Contents for Rockwell Automation 1606-XLS960F
Page 1
Switched Mode Power Supply Catalog Number 1606-XLS960F Reference Manual Original Instructions...
Page 2
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
Product features include: • AC 100…240V wide-range input • Width 125 mm (4.9 in.) • 95.0% full load and excellent partial load efficiencies • 50% BonusPower, 1440 W for up to 4 s Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
1900 g (4.2 lb) — (1) Between 85…90V AC. See Environment on page Catalog Numbers Cat. No. Descriptions Power supply 1606-XLS960F (48…54V standard unit) 1606-XLC Wall mount bracket 1606-XLSBUFFER48 Buffer unit 1606-XLSRED40HF Redundancy module Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
A: 100 V AC 0.95 B: 120 V AC C: 230 V AC A: 100V AC 0.85 B: 120V AC C: 230V AC Output Current Output Current 0.75 20 A 18 20 A Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Figure 8 on page 7 Up to 10 ms, output voltage stays above 40V, see Figure 10 on page 7. This peak current is available once every second. See Peak 55 A Current Capability on page Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Page 9
Figure 10 - Dynamic Overcurrent Capability, Typ Output Voltage (dynamic behavior, < 10 ms) Output Current Adjustment Normal Normal Short -circuit Range operation operation 35 A 17 s 17 s 17 s Output Current 70 A Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Hold-up Time Zero Transition 60 ms 48V, 10 A, typ Input 48V, 10 A, min Voltage 48V, 20 A, typ - 5% Output 48V, 20 A, min Voltage Hold-up Time Input Voltage 230V AC Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
(via external down collector) down Input voltage Input Input OFF: linked OFF: U < 1V OFF: I > 0.3 mA ON : open ON : U = 4…29V ON : I < 0.1 mA Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Figure 22 - Losses Versus Output Current at 48V, Typ Efficiency Power Losses 80 W 100V AC 230V AC 120V AC 230V AC Output Current Output Current 20 A 16 16 20 A Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
DC-OK LED DC-OK Contact Normal mode Closed During BonusPower Closed Overload (Hiccup mode) Flashing Open Output short circuit Flashing Open Temperature shut-down Flashing Open Active shut-down input Flashing Open No input power Open Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
1,000,000 hr means that statistically one unit fails every 100 hours if 10,000 units are installed in the field. However, the running time of individual failed units cannot be determined. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
(2) Do not use longer wires than 30 m (98.42 ft) for the shutdown input or use an additional protection. (3) Criterion A is fulfilled for output current up to 15 A. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
(1) The same as the ambient temperature and is defined as the air temperature 20 mm (0.79 in.) below the unit. (2) Do not energize while condensation is present. (3) Higher levels are allowed when using the 1606-XLC wall mounting bracket. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
(2 s up and 2 s down). Connect all input terminals together and connect all output poles before conducting the test. When testing, set the cutoff current settings to the values in the following table. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Temperature Code: T3 Groups: A, B, C, and D DNV-GL Certificate DNV-GL Type approved product Temperature: Class D Marine (DNV GL) Humidity: Class B Vibration: Class C EMC: Class A Enclosure: Class A Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
20 A each, which are individually decoupled by using mosfet technology. The output current is up to 40 A. Mosfets are used instead of diodes to reduce the heat generation and voltage drop between input and output. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Use the maximum duty cycle curve in Figure 39 on page 21 to check if the average output current is below the nominal current. • The duty cycle must be below 0.75. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Page 23
960 W >25 s 1440 W >1.3 s 1200 W 480 W >0.75 s 1440 W 480 W 0.1 s >0.16 s 1440 W 480 W >1.6 s 1440 W 480 W >4.9 s Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
The maximum allowed feed back voltage is 63V DC. The absorbing energy can be calculated according to the built-in large-sized output capacitor, which is specified in Output on page Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
The recommended end-of-charge voltage of 55V at 20 °C (68 °F) for four 12V VRLA lead-acid batteries in series cannot be supplied from the 1606-XLS960F power supply unit. Output Circuit Breakers Standard miniature circuit breakers, such as MCB or UL1077, are commonly used for AC-supply systems and can be used on DC branches.
60 °C (140 °F). Understand that leakage current, EMI, inrush current, and harmonics increase when using multiple power supply units. Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Figure Figure 44 - Daisy Chain of Outputs Figure 45 - Using Distribution Terminals Distribution Terminals Power Power Power Power Supply Supply Supply Supply Load Load Output Output Output Output 25 A Continuous Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Figure 47 - Operation on Two Phases Power Supply The power supply unit can be used internal on two phases of a three-phase fuse system, as long as the supplying +10% voltage is below 240V Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Temperature rise 41.5K (1) The load is placed outside the box. (2) Temperature in the middle of the right side of the power supply unit with a distance of 20 mm (0.79 in.). Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
60 °C Output Current 20 A Figure 51 - Mounting Orientation D: Horizontal CW Ambient Temperature 60 °C Output Current 20 A Figure 52 - Mounting Orientation E: Horizontal CCW Ambient Temperature 60 °C Rockwell Automation Publication 1606-RM028A-EN-P - September 2021...
Switched Mode Power Supply Reference Manual Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Switched Mode Power Supply Specifications Technical Data, publication Provides specifications for Bulletin 1606 products and applications. 1606-TD002 1606-XLS960F Installation Instructions, publication 1606-IN029 Provides basic specifications and installation instructions.
Page 32
At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc.